FIR10-00202
| INSP-Final Inspection | 3/24/2011 | 3/24/2011 | 3/25/2011 1:28:43 PM | P | NR |
|
|
robert Phone #: ###-####
|
BLD10-02661
| FIRE-Final Inspection | 3/24/2011 | 3/24/2011 | 3/24/2011 3:31:21 PM | P | FAIL |
|
|
Missing premise identification, remove manual thumbturns at two locations including the main entry/exit.
|
FIR11-00009
| INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 3:29:42 PM | P | PASS |
|
|
Fire sprinkler permit finaled. Inspection passed.
|
FIR11-00036
| INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 3:28:59 PM | P | PASS |
|
|
Fire sprinkler work passed inspection, permit finaled.
|
FIR10-00523
| INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 3:28:10 PM | A | NR |
|
|
Forrest/Troy, They want to do a temp occupancy on the Showroom side of the original building. The only part of the fire alarm install not complete is the (2) duct detectors. They have not changed out the HVAC units yet, so the duct detectors are not operational. Please call me and let me know if this will work. Thanks, Jason ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick
|
FIR10-00538
| INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 3:27:50 PM | P | PASS |
|
|
Field verified adjustments, inspection passed. Permit finaled.
|
FIR10-00579
| INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 12:39:19 PM | A | FAIL |
|
|
Final pending forward flow test sufficient to meet system demand, reliable heating at the riser room to maintain ambient temperature above 40 deg., signage at the doors to the riser. Alarm interconnections tested okay.
|
FIR10-00656
| INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 12:32:40 PM | A | FAIL |
|
|
Final pending correct length sample tube at duct detectors 2 and 3, RTU 1 is not powered at this time, provide cover plate at riser room junction box, label spare FPL at the panel and the riser room, provide locks at the panel circut breaker. Points map and door signage posted while on site. Sprinkler monitoring, FACP, AES and offsite signals okayed.
|
FIR11-00117
| INSP-Sprinkler Rough-in/Hydro | 3/23/2011 | 3/24/2011 | 3/24/2011 12:26:58 PM | A | PART |
|
|
Overhead fire sprinkler modifications at the new drop ceilings are okay for cover. Note: two intermediate temp concealed heads as marked on plans will need to be provided with 165 deg. escutcheons per submital.
|
BLD10-00842
| FIRE-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 12:22:20 PM | A | PASS |
|
|
Fire life safety final approved.
|
FIR10-00415
| INSP-Final Inspection | 3/22/2011 | 3/24/2011 | 3/24/2011 12:21:18 PM | A | PASS |
|
|
Corrections finished. Fire alarm passed final inspection.
|
FIR10-00470
| INSP-Sprinkler Rough-in/Hydro | 3/23/2011 | 3/24/2011 | 3/24/2011 12:00:00 AM | A | PASS |
|
|
Passed hydro.
Steph Phone #: ###-####
|
FIR10-00514
| INSP-Sprinkler Rough-in | 3/23/2011 | 3/24/2011 | 3/24/2011 12:00:00 AM | A | PASS |
|
|
Passed one sprinkler in riser room as a rough in.
Steph Phone #: ###-####
|