BLD12-00800
| FIRE-Final Inspection | 3/24/2014 | 3/24/2014 | 3/24/2014 3:25:21 PM | P | PART |
|
|
Life safety passed for the new Customer Louge Area.
|
FIR14-00154
| INSP-Alarm Testing | 3/24/2014 | 3/24/2014 | 3/24/2014 3:03:04 PM | P | DONE |
|
|
John Phone #: ###-####
|
FIR14-00110
| INSP-Sprinkler Rough-in/Hydro | 3/20/2014 | 3/24/2014 | 3/24/2014 3:01:27 PM | A | PASS |
|
|
Overhead hydro test of the pre-action system passed. Rough-in passed. Piping can be covered.
|
BLD13-02573
| FIRE-Final Inspection | 3/21/2014 | 3/24/2014 | 3/24/2014 10:49:40 AM | A | PASS |
|
|
Life safety passed
|
BLD12-00800
| FIRE-Final Inspection | 3/20/2014 | 3/24/2014 | 3/24/2014 10:38:43 AM | A | FAIL |
|
|
The power was cut/off and no exit signs/emergency lights were working. Electrician was working on it.
|
FIR14-00154
| INSP-Final Inspection | 3/24/2014 | 3/24/2014 | 3/24/2014 10:23:11 AM | A | FAIL |
|
|
All items test ok except the correct orfice is not in the fire sprinkler inspectors test line. So flow switch could not be tested/verified.
|
FIR13-00690
| INSP-Final Inspection | 3/21/2014 | 3/24/2014 | 3/24/2014 10:15:50 AM | A | PASS |
|
|
life safety passed
|
BLD13-03564
| FIRE-Final Inspection | 3/21/2014 | 3/24/2014 | 3/24/2014 9:18:12 AM | A | FAIL |
|
|
Smoke evac system is non-functional. The new duct smoke detector is non-functional. All other life safety items are ok.
|