ELE13-00375 ELE-Aging Inspection3/24/20153/24/20153/30/2015 8:26:49 AM DONE
Still under construction
ELE13-00214 Final3/24/20153/24/20153/24/2015 4:20:43 PMPPASS
Drove by corrections made. Final ok
ELE15-00590 Final3/24/20153/24/20153/24/2015 4:17:54 PMPCANC
Contact: Brian Gee.... Perm. service ; Final inspections please Phone #: ###-#### Inspection requested via web by Deb Gooden Need to reschedule final to ensure GFCI and lighting working properly.
ELE15-00590 Permanent Service3/24/20153/24/20153/24/2015 4:17:12 PMPPASS
Contact: Brian Gee.... Perm. service ; Final inspections please Phone #: ###-#### Inspection requested via web by Deb Gooden p/s o/h n ok
ELE15-00765 Conference3/23/20153/24/20153/24/2015 3:29:41 PMPDONE
Please give me a half hour heads up so I can meet you out there. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan Discussed requirements for service change to eliminate tripping due to overload on house panel that feeds community laundry room. Shall up size service to house panel, fuse down feeders to appartments due to SER cable sub feeds, raise riser over flat roof, relocate house panel in laundry room panel to provide work space, did permit search no other recent permits exist. Noticed dated Dec 2013 NM cable ran outdoors under walkway roof to carport. Contractor to inform building management all needs replaced with listed materials for locations.
ELE14-03132 Electrical Rough-In3/24/20153/24/20153/24/2015 2:46:55 PMPPASS
Please inspect underground on gate wiring Phone #: ###-#### Inspection requested via web by ERIC CENTERS Underground for gate east side rough in ok cover
ELE15-00779 Permanent Service3/24/20153/24/20153/24/2015 2:30:15 PMPPASS
2nd rod and plumbing bond at water heater between hot and cold for final. p/s u/g rec ok
ELE15-00779 Final3/24/20153/24/20153/24/2015 2:29:01 PMPCANC
This is a foreclosure.. I walked the house and opened the service to check wires and terminations. I need to have power to check remainder of house. Please call me with any questions. 208 ###-#### Todd
Please call for access..
Phone #: ###-#### Inspection requested via web by Kendra Lanham Needed permenant service
ELE15-00757 Rough-In Permanent Service3/24/20153/24/20153/24/2015 2:09:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
ELE15-00087 Electrical Rough-In3/24/20153/24/20153/24/2015 1:51:06 PMPPASS
Ditch inspection // Rocky Phone #: ###-#### Underground to shed rough in ok cover
ELE15-00470 Final3/24/20153/24/20153/24/2015 1:17:12 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
ELE13-00824 Final3/24/20153/24/20153/24/2015 12:39:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE15-00354 Final3/24/20153/24/20153/24/2015 12:24:25 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov 210.12(A)- All 15 and 20 amp 120 volt outlets shall have AFCI protection.
ELE15-00762 Temporary Service3/23/20153/24/20153/24/2015 11:13:37 AMPPASS
Phone #: ###-#### Inspection requested via web by Eric Schroeder t/s u/g n ok
ELE15-00672 Rough-In Permanent Service3/23/20153/24/20153/24/2015 11:00:07 AMAPASS
Please contact Cody ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE15-00757 Final3/24/20153/24/20153/24/2015 10:26:03 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
ELE15-00757 Rough-In Permanent Service3/23/20153/24/20153/24/2015 10:10:22 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52(A)- Wall in nook, receptacle outlet shall be located within 6' of door to hall.
210.52(I)- Foyer wall with 3' minimum length shall have receptacle outlet installed.
334.23 NM cable located within 7' of attic access shall be protected with guard strips.
ELE15-00768 Rough-In Permanent Service3/23/20153/24/20153/24/2015 9:37:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Jerry Moore rough in ok cover p/s u/g n ok
ELE15-00440 Permanent Service3/23/20153/24/20153/24/2015 8:37:13 AMAPASS
Toby is the contact. Fire pump service. Phone #: ###-#### Inspection requested via web by Buster Bowen Corrections made p/s u/g n ok
ELE15-00461 Final3/23/20153/24/20153/24/2015 8:10:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Betty Final ok