Inspections for the day of: Tuesday, March 24, 2015.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-00076 FIRE-Final Inspection3/23/20153/24/20153/24/2015 3:33:29 PMACANC
Curtis Phone #: ###-####
FIR15-00158 INSP-Final Inspection3/23/20153/24/20153/24/2015 3:29:59 PMPFAIL
Could not final permit until flow switches are able to be tested.
BLD14-02997 FIRE-Final Inspection3/24/20153/24/20153/24/2015 3:28:41 PMPFAIL
Will be ok to final when the project related fire alarm and fire sprinkler permits are finaled.
FIR15-00040 INSP-Sprinkler Rough-in/Hydro3/24/20153/24/20153/24/2015 3:26:40 PMPPASS
Overhead hydro test passed. Remaining piping can be covered.
FIR14-00848 INSP-Final Inspection3/23/20153/24/20153/24/2015 3:15:54 PMPCANC
Mike B is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD15-00817 FIRE-Final Inspection3/24/20153/24/20153/24/2015 1:50:18 PMPPASS
Life safety passed
FIR15-00130 INSP-Sprinkler Rough-in3/24/20153/24/20153/24/2015 1:49:25 PMPFAIL
Ceiling tile has been installed in the Pharmacy without approval for cover. Tile to be removed for inspection.
FIR14-00623 INSP-Sprinkler Rough-in/Hydro3/24/20153/24/20153/24/2015 1:15:27 PMPPASS
Overhead hydro test passed
FIR14-00618 INSP-Sprinkler Rough-in3/24/20153/24/20153/24/2015 12:59:59 PMPFAIL
Inspection was for tenting. Tenting is not complete. (Two trips)
FIR14-00722 INSP-Final Inspection3/23/20153/24/20153/24/2015 9:52:06 AMAFAIL
Alarm signals register as supervisory and hvac units have not been turned on to verify duct smoke detector shut down. No electric alarm bell has been installed to flow switch.
FIR14-00602 INSP-Final Inspection3/20/20153/24/20153/24/2015 9:49:14 AMAFAIL
No outside electric alarm bell has been installed. Flow switch comes in at the FACP as a supervisory signal. No signage on riser room door.
FIR15-00134 INSP-Final Inspection3/23/20153/24/20153/24/2015 8:52:37 AMAPASS
Permit finaled
BLD15-00761 FIRE-Final Inspection3/23/20153/24/20153/24/2015 8:36:07 AMAPASS
Life safety passed. Thumb turn dead bolt removed as I waited from office door.
BLD15-00587 FIRE-Final Inspection3/23/20153/24/20153/24/2015 8:35:16 AMAPASS
Life safety passed