ELE97-00853
| INSP - Permanent service | 3/25/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | | FAIL |
|
|
/ / 315 - 53 failed jf cor. posted NEC, T250-94 #4 to electrode and wa 250-80 shall remove #6 bond wire from sub panels,to water system, 110-14 use noalox on all alluminum connections, 250-92(b) use connector to pass through at service pan
|
ELE97-00902
| INSP - Ele Rough-In/Perm Svc | 3/24/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | A | PASS |
|
|
03/25/97 315 - 09&53 ok jf 8rms 1a/c 200a u/g new
|
ELE97-00903
| INSP - Ele Rough-In/Perm Svc | 3/24/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | A | PASS |
|
|
03/25/97 315 - 09&53 ok jf 10rms 1a/c 200a u/g new
|
ELE97-00904
| INSP - T/S and Final | 3/25/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | A | PASS |
|
|
|
ELE96-03771
| INSP - Ele Rough-In/Perm Svc | 3/24/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | A | CANC |
|
|
03/25/97 315 - PLEASE TALK TO DON WHEN YOU GET THERE cancel see added
|
ELE97-00348
| INSP - Final | 3/20/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | A | PASS |
|
|
03/25/97 315 - late a.m. as close to noon as possible 14 ok jf
|
ELE97-00489
| INSP - Final | 3/24/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | A | CANC |
|
|
03/25/97 315 - canceled by contractor jf
|
ELE97-00853
| INSP - Permanent service | 3/24/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | A | CANC |
|
|
03/25/97 315 - need to check with JSchmer on 53 jf
|
ELE97-00715
| INSP - Final | 3/25/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | P | PASS |
|
|
03/25/97 315 - STE 125 14 ok jf
|
ELE97-00135
| INSP - Final | 3/25/1997 | 3/25/1997 | 3/25/1997 12:00:00 AM | P | PASS |
|
|
03/25/97 315 - 14 ok jf
|