ELE05-00990
| Permanent Service | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | FAIL |
|
|
cor. posted called needs #4 for concrete encased electrode , 550.32(A) or (B) service not allowed on mobile home unlees requirements of 550.32(B) are met 3/25/2005 8:12:02 AM
|
ELE05-00533
| Final | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/24/2005 at 5:36:56 PM. Contact: ###-####. ok 3/25/2005 10:31:08 AM
|
ELE05-00283
| Conference | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | DONE |
|
|
Scheduled by a contractor via Hello! on 3/24/2005 at 10:03:54 AM. Contact: ###-####. cor. posted met contractor 210.5(C), 200.6(D), 225.37, 314.28(A)(2), 250.52(A)(1),58,104(A)(1), 110.2,3 spray booth and furnace not listed or tested 3/25/2005 9:52:33 AM
|
ELE05-00989
| Conference | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | CANC |
|
|
Andy-Bonding insp.; Phone #: ###-#### Internet Inspection Request from: Jan Rice see added r/i for pool bond 3/25/2005 11:56:00 AM
|
ELE05-00989
| Electrical Rough-In | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | PART |
|
|
pool bond and u/g for pool light ok
|
ELE04-01545
| Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
p/s u/g new ok
|
ELE04-01545
| Electrical Rough-In | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/24/2005 at 1:34:12 PM. Contact: ###-####. ok 3/25/2005 1:59:28 PM
|
ELE05-00994
| Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | FAIL |
|
|
dave ###-#### cor. posted called 250.140,142 needs 4 wire circuits , pigtails, rececpts from sub panel to range and dryer, 250.53(D)(2),56 2 grd rods, 408.4 label panel as code noted states 3/25/2005 4:23:14 PM
|
ELE05-00345
| Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g new ok 3/25/2005 3:07:16 PM
|
ELE05-00897
| Final | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
steve; Phone #: ###-#### Note: please call 1/2 hr prior to inspection Internet Inspection Request from: Cathy Chiles ok card signed 3/25/2005 3:42:51 PM
|
ELE05-00063
| Final | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 3/25/2005 1:05:05 PM
|