ELE05-00857
| Rough-In Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 9:32:35 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 3/25/2005 at 9:12:02 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Mar 25 2005 9:32AM.
|
ELE05-00985
| Rough-In Permanent Service | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | PART |
|
|
Call Francis with any questions. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa called contr, ri not ready, doing some framing, p/s u/g n ok 3/25/2005 8:10:22 AM
|
ELE05-00817
| Rough-In Permanent Service | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/24/2005 at 2:13:46 PM. Contact: ###-####. called contr, left message, still need nail plates up bath, up bedroom, stairs, living room, garage. re-inspection fee due. 300.4 (A)(1) and (D) 3/25/2005 8:49:39 AM
|
ELE05-00867
| Electrical Rough-In | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 3/25/2005 at 5:39:45 AM. Contact: ###-####. customer service area clg only ok to cover. left corr notice:BCC no violations shall be retained, 314.23(A) boxes shall be mounted rigidly, 406.5 recpts shall have faceplates. called contr 3/25/2005 9:42:41 AM
|
ELE05-00277
| Final | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
Please final tenant space A. Core portion of the building will still be active for one more tennant space. If you have any questions please call. ; Phone #: ###-#### Internet Inspection Request from: David Mackey ok to final 3/25/2005 4:04:07 PM
|
ELE05-00860
| Electrical Rough-In | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/24/2005 at 2:24:26 PM. Contact: ###-####. ric ok walls except front entry. 3/25/2005 12:45:14 PM
|
ELE05-00995
| Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | FAIL |
|
|
###-#### - brent called contr, left corr notice, 250.53(B) electrodes shall be min 6' apart, 250...53(G) electrode shall be driven to full depth or less than 45 degrees, 110.12(A) unused openings shall be closed 3/25/2005 1:21:06 PM
|
ELE04-02595
| Electrical Rough-In | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 3/25/2005 at 11:05:41 AM. Contact: ###-####. meeting room hard lid ok to cover, walls in lobby area ok to cover. pool rail bonding for ladder ok, but not for handrail since one of the anchors didn't have the ground wire connected. will need to re-check pool. 3/25/2005 4:33:28 PM
|
ELE05-00998
| Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
###-#### remco p/s u/g n ok 3/25/2005 1:34:30 PM
|