FIR04-00664
| INSP-Sprinkler Rough-in | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | PART |
|
|
See city approved plans for rooms that piping can be covered and for locations of deficiencies at these same rooms 3/25/2005 10:45:07 AM
|
BLD04-02708
| FIRE-Final Inspection | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | A | FAIL |
|
|
dave; Phone #: ###-#### The emergency light at the north side of the elevator lobby has not been installed yet. 3/25/2005 10:44:26 AM
|
BLD04-02887
| FIRE-Final Inspection | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | CANC |
|
|
Not ready 3/25/2005 3:05:10 PM
|
MIS05-00030
| FIR-Final | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 3/25/2005 11:11:04 AM
|
BLD04-01997
| FIRE-Final Inspection | 3/24/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | FAIL |
|
|
No approved plans on site. No inspection performed. 3/25/2005 3:35:11 PM
|
FIR05-00005
| INSP-Final Inspection | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled 3/25/2005 10:58:09 AM
|
FIR05-00103
| INSP-Sprinkler Rough-in/Hydro | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
Underground supply and the fdc supply is ok to cover 3/25/2005 11:12:06 AM
|
BLD05-00298
| FIRE-Final Inspection | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/25/2005 at 9:43:48 AM. Contact: ###-####. Make north exit accessible and test light. Add exit/emergency light in corridor by womens restroom. Repair exit light in storage. Install fire extinguishers. Install door hardware on doors in remodeled area. 3/25/2005 1:09:52 PM
|
BLD05-00440
| FIRE-Final Inspection | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 3/25/2005 11:26:29 AM
|
FIR04-00749
| INSP-Sprinkler Rough-in | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | PASS |
|
|
george richardson ###-#### Underground fire supply and fdc connection ok to cover, verify gravel install below ball drip. 3/25/2005 1:13:04 PM
|
BLD04-02863
| FIRE-Final Inspection | 3/25/2005 | 3/25/2005 | 3/25/2005 12:00:00 AM | P | FAIL |
|
|
Remove the thumbturn from the main exit, lower fire extinguishers to 48" max and provide annual inspection for all fire extinguishers, provide approved door hardware on restroom door, rear exit door and the half door, provide minimum 4" high address numbers 3/25/2005 1:57:33 PM
|