Inspections for the day of: Tuesday, March 25, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00225 Electrical Rough-In3/24/20083/25/20083/25/2008 3:55:44 PMPPASS
please call Duke if needed for above ceiling inspection on 2nd floor. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey large office and conference room ceilings ok to cover
ELE08-00442 Electrical Rough-In3/25/20083/25/20083/25/2008 2:45:58 PMPPASS
CONTACT: SHANE KORTE Phone #: ###-#### Internet Inspection Request from: Deb Gooden walls only ok to cover
ELE08-00128 Final3/25/20083/25/20083/25/2008 1:25:14 PMPFAIL
michael Phone #: ###-#### met owner, left correction notice, NEC 406.4(D) receptacles face shall be flush with or project from faceplate, 406.4 receptacles shall be securely fastened in place, 422.31 shall provide lock-outs for dishwashers, BCC all equipment shall be installed- air conditioners, panel screws shall be installed, shall permanently id units at service
ELE08-00687 Temporary Service3/25/20083/25/20083/25/2008 12:25:25 PMPPASS
jay Phone #: ###-#### corrections made, t/s o/h n ok
ELE08-00700 Rough-In Permanent Service3/24/20083/25/20083/25/2008 10:32:09 AMAPASS
Greg ###-####//call for gate code ric ok, called contractor, p/s, exst meter pak, rec, ok, 1 meter only
ELE08-00370 Final3/24/20083/25/20083/25/2008 10:13:35 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to final, signed occupancy card
ELE08-00318 Electrical Rough-In3/24/20083/25/20083/25/2008 9:47:26 AMAPASS
UFFER GROUND MORGAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok for concrete encased electrode, using clamp approved for concrete encasement
ELE08-00693 Electrical Rough-In3/25/20083/25/20083/25/2008 9:19:10 AMAPASS
rough in and service inspection
The old service is just temporary conected to a cord to keep the furnace running, I will remove it this morning. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ric ok
ELE08-00693 Permanent Service3/25/20083/25/20083/25/2008 8:48:45 AMAPASS
rough in and service inspection
The old service is just temporary conected to a cord to keep the furnace running, I will remove it this morning. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig p/s u/g n ok
ELE08-00702 Temporary Service3/24/20083/25/20083/25/2008 8:46:17 AMAPASS
JOHN Phone #: ###-#### t/s o/h n ok
ELE08-00536 Final3/24/20083/25/20083/25/2008 8:06:26 AMAFAIL
butch Phone #: ###-#### called contractor, left correction notice, NEC 314.25 each box shall have cover installed, 314.23 boxes shall be securely supported, 358.30 emt shall be securely supported within 3' of termination, 210.62 shall install show window outlet directly above show window, 725.3 abandoned low voltage cables shall be removed, BCC all work shall be done before inspection, no violations shall be retained