ELE08-00225
| Electrical Rough-In | 3/24/2008 | 3/25/2008 | 3/25/2008 3:55:44 PM | P | PASS |
|
|
please call Duke if needed for above ceiling inspection on 2nd floor. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey large office and conference room ceilings ok to cover
|
ELE08-00442
| Electrical Rough-In | 3/25/2008 | 3/25/2008 | 3/25/2008 2:45:58 PM | P | PASS |
|
|
CONTACT: SHANE KORTE Phone #: ###-#### Internet Inspection Request from: Deb Gooden walls only ok to cover
|
ELE08-00128
| Final | 3/25/2008 | 3/25/2008 | 3/25/2008 1:25:14 PM | P | FAIL |
|
|
michael Phone #: ###-#### met owner, left correction notice, NEC 406.4(D) receptacles face shall be flush with or project from faceplate, 406.4 receptacles shall be securely fastened in place, 422.31 shall provide lock-outs for dishwashers, BCC all equipment shall be installed- air conditioners, panel screws shall be installed, shall permanently id units at service
|
ELE08-00687
| Temporary Service | 3/25/2008 | 3/25/2008 | 3/25/2008 12:25:25 PM | P | PASS |
|
|
jay Phone #: ###-#### corrections made, t/s o/h n ok
|
ELE08-00700
| Rough-In Permanent Service | 3/24/2008 | 3/25/2008 | 3/25/2008 10:32:09 AM | A | PASS |
|
|
Greg ###-####//call for gate code ric ok, called contractor, p/s, exst meter pak, rec, ok, 1 meter only
|
ELE08-00370
| Final | 3/24/2008 | 3/25/2008 | 3/25/2008 10:13:35 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to final, signed occupancy card
|
ELE08-00318
| Electrical Rough-In | 3/24/2008 | 3/25/2008 | 3/25/2008 9:47:26 AM | A | PASS |
|
|
UFFER GROUND MORGAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok for concrete encased electrode, using clamp approved for concrete encasement
|
ELE08-00693
| Electrical Rough-In | 3/25/2008 | 3/25/2008 | 3/25/2008 9:19:10 AM | A | PASS |
|
|
rough in and service inspection The old service is just temporary conected to a cord to keep the furnace running, I will remove it this morning. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ric ok
|
ELE08-00693
| Permanent Service | 3/25/2008 | 3/25/2008 | 3/25/2008 8:48:45 AM | A | PASS |
|
|
rough in and service inspection The old service is just temporary conected to a cord to keep the furnace running, I will remove it this morning. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig p/s u/g n ok
|
ELE08-00702
| Temporary Service | 3/24/2008 | 3/25/2008 | 3/25/2008 8:46:17 AM | A | PASS |
|
|
JOHN Phone #: ###-#### t/s o/h n ok
|
ELE08-00536
| Final | 3/24/2008 | 3/25/2008 | 3/25/2008 8:06:26 AM | A | FAIL |
|
|
butch Phone #: ###-#### called contractor, left correction notice, NEC 314.25 each box shall have cover installed, 314.23 boxes shall be securely supported, 358.30 emt shall be securely supported within 3' of termination, 210.62 shall install show window outlet directly above show window, 725.3 abandoned low voltage cables shall be removed, BCC all work shall be done before inspection, no violations shall be retained
|