Inspections for the day of: Tuesday, March 25, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00048 INSP-Sprinkler Rough-in/Hydro3/25/20083/25/20083/25/2008 4:52:02 PMPPART
OH rough-in approved for cover.
FIR07-00935 INSP-Sprinkler Rough-in/Hydro3/25/20083/25/20083/25/2008 4:49:32 PMPNR
Not completed for inspection.
FIR06-00587 INSP-Final Inspection3/25/20083/25/20083/25/2008 4:47:19 PMPPASS
Fire sprinkler permit finaled.
FIR08-00109 INSP-Conference3/25/20083/25/20083/25/2008 4:45:28 PMPDONE
Regarding field modifications not reflected on stamped plan set.
BLD06-01994 BLD-Conference3/25/20083/25/20083/25/2008 12:16:45 PMADONE
Project related fire alarm and sprinkler permits are complete, occupancy approval pending satisfactory fire life safety inspection-see fire code review notes attatched to the stamped plan set for requirements and conditions.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro3/24/20083/25/20083/25/2008 11:59:04 AMAPART
Accepted photographic documentation of seismic bracing at four locations including the plaza level NE, NW, SE, and SW corner 4-way braces inaccessible for viewing due to confined space and asbestos abatement. Images attached under "Documents"
FIR08-00073 INSP-Final Inspection3/24/20083/25/20083/25/2008 11:52:17 AMAPASS
Fire alarm testing passed, main entry door mag lock interconnection to the FACP also tested, permit finaled.
BLD08-00428 FIRE-Conference3/24/20083/25/20083/25/2008 11:50:13 AMADONE
On site conference regarding necessary modifications to the existing fire sprinkler system due to building remodel work.