Inspections for the day of: Wednesday, March 25, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00824 FIR-Aging Inspection3/25/20093/25/20094/1/2009 7:28:19 AM PASS
Permit has been finaled
FIR08-00540 INSP-Final Inspection3/25/20093/25/20093/25/2009 4:44:10 PMPPASS
Permit was previously finaled by Ken Roule
FIR08-00504 INSP-Supply line flush3/24/20093/25/20093/25/2009 3:28:35 PMPPASS
The flush of the underground supply line passed.
FIR09-00146 INSP-Conference3/25/20093/25/20093/25/2009 3:22:46 PMPPASS
I confirmed with Larren that I would only require a hydro test on the replaced/recalled sprinkler heads as per NFPA 25. I would consider the three non-recall dry pendants a maintenance issue which they could replace at their leisure without being included with the hydro testing.
FIR08-00778 INSP-Sprinkler Rough-in/Hydro3/25/20093/25/20093/25/2009 2:10:17 PMAPART
There are four deficiencies prior to final sign off. The heads at the top and bottom of the elevator shaft are not oriented correctly. The sprinkler piping to the head at the bottom of the shaft is not secured and needs a cage. One head on the second floor is bent and needs replaced and one upright sprinkler head in a warehouse storage room is blocked by a pendant light. Also the pre-action system has not been tested. The other deficiencies have been corrected and marked off on the city approved plans.
FIR09-00116 INSP-Conference3/25/20093/25/20093/25/2009 1:28:49 PMPPASS
Scotty wanted to know if a record of completion would be required for this project. For this small scope of work I would not need them.
BLD09-00220 FIRE-Final Inspection3/24/20093/25/20093/25/2009 12:22:42 PMAPASS
Life safety passed
BLD06-03303 FIRE-Final Inspection3/24/20093/25/20093/25/2009 10:01:39 AMAPASS
life safety passed. SimplexGrinnell will have the fire extinguishers tagged later this morning