FIR10-00014
| INSP-Sprinkler Rough-in | 3/24/2010 | 3/25/2010 | 3/25/2010 3:45:57 PM | A | PART |
|
|
The sprinkler piping rough-in is ok except for the lag bolts on the earthquake bracing attachments need to be changed to through bolts with the correct length and blocking as discussed. Could not make it back for a re-inspection/cover approval so Ken is scheduling for tomorrow morning.
|
BLD09-02300
| FIRE-Final Inspection | 3/25/2010 | 3/25/2010 | 3/25/2010 3:42:50 PM | P | FAIL |
|
|
The inspection turned into a conference. Plans are going to be resubmitted showing changes in the exiting path. Also the new doors in the new addition need approved single action hardware installed and fire extinguishers need installed as discussed.
|
BLD09-01934
| FIRE-Final Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 3:32:39 PM | P | FAIL |
|
|
All items are ok except the fume room does not have an audio/visual device. One needs to be added, utilizing the permit process or periferial effects need to be verified as allowed per NFPA 72. There is a soffit blocking the adjacent a/v .
|
FIR10-00093
| INSP-Final Inspection | 3/25/2010 | 3/25/2010 | 3/25/2010 3:25:04 PM | P | PASS |
|
|
Permit finaled.
|
BLD10-00513
| FIRE-Final Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 3:06:01 PM | P | PASS |
|
|
Life safety passed. Building inspector to please verify single action hardware on the rear exit door.
|
FIR09-00708
| INSP-Sprinkler Rough-in | 3/24/2010 | 3/25/2010 | 3/25/2010 2:35:31 PM | P | PASS |
|
|
The three rooms near the nurses station are now ok to cover.
|
BLD10-00516
| FIRE-Final Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 11:16:24 AM | P | PASS |
|
|
Life safety passed. The smoke evac system functioned correctly.
|
FIR10-00116
| INSP-Final Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 11:15:50 AM | P | PASS |
|
|
Permit finaled
|
FIR03-00052
| FIR-Aging Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 11:13:43 AM | A | NR |
|
|
wip
|
BLD10-00340
| FIRE-Conference | 3/24/2010 | 3/25/2010 | 3/25/2010 11:13:26 AM | A | PART |
|
|
A temporary occupancy was given until the door hardware is removed, door locked and the exit sign removed or blanked off on the east storefront door as per the approved plans.
|
FIR09-00688
| FIR-Aging Inspection | 3/25/2010 | 3/25/2010 | 3/25/2010 8:56:33 AM | | NR |
|
|
I spoke to Lori and she did not know the status of the project. She was going to talk to Bill.
|
BLD09-02286
| FIRE-Final Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 8:17:09 AM | A | PASS |
|
|
Life safety passed.
|