Inspections for the day of: Thursday, March 25, 2010.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00014 INSP-Sprinkler Rough-in3/24/20103/25/20103/25/2010 3:45:57 PMAPART
The sprinkler piping rough-in is ok except for the lag bolts on the earthquake bracing attachments need to be changed to through bolts with the correct length and blocking as discussed. Could not make it back for a re-inspection/cover approval so Ken is scheduling for tomorrow morning.
BLD09-02300 FIRE-Final Inspection3/25/20103/25/20103/25/2010 3:42:50 PMPFAIL
The inspection turned into a conference. Plans are going to be resubmitted showing changes in the exiting path. Also the new doors in the new addition need approved single action hardware installed and fire extinguishers need installed as discussed.
BLD09-01934 FIRE-Final Inspection3/24/20103/25/20103/25/2010 3:32:39 PMPFAIL
All items are ok except the fume room does not have an audio/visual device. One needs to be added, utilizing the permit process or periferial effects need to be verified as allowed per NFPA 72. There is a soffit blocking the adjacent a/v .
FIR10-00093 INSP-Final Inspection3/25/20103/25/20103/25/2010 3:25:04 PMPPASS
Permit finaled.
BLD10-00513 FIRE-Final Inspection3/24/20103/25/20103/25/2010 3:06:01 PMPPASS
Life safety passed. Building inspector to please verify single action hardware on the rear exit door.
FIR09-00708 INSP-Sprinkler Rough-in3/24/20103/25/20103/25/2010 2:35:31 PMPPASS
The three rooms near the nurses station are now ok to cover.
BLD10-00516 FIRE-Final Inspection3/24/20103/25/20103/25/2010 11:16:24 AMPPASS
Life safety passed. The smoke evac system functioned correctly.
FIR10-00116 INSP-Final Inspection3/24/20103/25/20103/25/2010 11:15:50 AMPPASS
Permit finaled
FIR03-00052 FIR-Aging Inspection3/24/20103/25/20103/25/2010 11:13:43 AMANR
wip
BLD10-00340 FIRE-Conference3/24/20103/25/20103/25/2010 11:13:26 AMAPART
A temporary occupancy was given until the door hardware is removed, door locked and the exit sign removed or blanked off on the east storefront door as per the approved plans.
FIR09-00688 FIR-Aging Inspection3/25/20103/25/20103/25/2010 8:56:33 AM NR
I spoke to Lori and she did not know the status of the project. She was going to talk to Bill.
BLD09-02286 FIRE-Final Inspection3/24/20103/25/20103/25/2010 8:17:09 AMAPASS
Life safety passed.