Inspections for the day of: Friday, March 25, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00987 FIRE-Conference3/25/20113/25/20113/28/2011 5:54:52 PMADONE
Regarding project schedule.
BLD11-00070 FIRE-Final Inspection3/25/20113/25/20113/28/2011 5:53:02 PMPNR
mark Phone #: ###-#### Discussed items needed for final. 3/25.
FIR10-00556 INSP-Sprinkler Rough-in3/24/20113/25/20113/25/2011 4:06:27 PMPPART
See approved plan set for area outlined in blue highlighter and initialed with today's date for locations approved for ceiling cover.
FIR10-00202 INSP-Alarm Testing3/25/20113/25/20113/25/2011 4:03:02 PMPFAIL
Noted mag lock at the north tenant server room did not drop out upon fire alarm activation- per plan this relay to be tied in. Also need verification the remainder of doors equiped with mag locks at the tenant spaces are in compliance as well.
FIR10-00202 INSP-Alarm Testing3/25/20113/25/20113/25/2011 1:34:45 PMAPART
Damper operation at the electrical room verified okay, alarm condition reported- however a zone 6 flow was recieved at central station in additon to the zone 5 SD. Clean agent alarm condition tested but did not latch, tape and plastic cover at one SD in the server room removed while on site.
BLD11-00478 FIRE-Final Inspection3/24/20113/25/20113/25/2011 1:28:26 PMAFAIL
Noted two fire extinguishers are overdue annual service, provide verification of a current annual inspection for the existing fire sprinkler system. No acess to the riser room.
BLD10-02661 FIRE-Final Inspection3/24/20113/25/20113/25/2011 1:25:33 PMAPASS
Reinspection passed, C/N items are complete. Manual thumbturns have been removed.
BLD11-00005 FIRE-Final Inspection3/24/20113/25/20113/25/2011 1:24:01 PMAPASS
Verified items on correction notice have been finished. Fire life safety inspection passed.