Inspections for the day of: Tuesday, March 25, 2014.
Number of inspections: 7
Percentage of inspections complete: 86 %
Percentage of inspections not complete: 14 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00181 FIRE-Conference3/19/20143/19/2014 P 
JC at phone #: ###-####
FIR13-00682 INSP-Conference3/24/20143/25/20144/4/2014 4:44:20 PMADONE
Ray McQueen Phone #: ###-####
FIR13-00704 INSP-Final Inspection3/24/20143/25/20143/25/2014 4:44:11 PMANR
Missing riser finish pack including calc stickers, DCVA certification, caps at FDC, sign at outside bell, riser tag, etc., need to complete forward flow, missing escutcheons.
FIR14-00084 INSP-Final Inspection3/24/20143/25/20143/25/2014 4:40:24 PMANR
Noted correction items include; cd setting at one classroom, two overspaced av's at entry vestibules, missing coverage at the womens restroom vestibule, provide relay to mag lock at the SE exit door, post points map, need record of inspection and testing forms, missing knox box.
FIR13-00720 INSP-Sprinkler Rough-in3/24/20143/25/20143/25/2014 4:35:34 PMPPART
Overhead work approved for cover. Need to provide QR head per plan at the restroom adjacent to the warehouse area, provide matched temp heads above the open office at one location, remove travel caps. Plans annotated.
FIR13-00440 INSP-Sprinkler Rough-in3/24/20143/25/20143/25/2014 2:18:01 PMAPART
Okay to cover overhead work at the first floor sheetrock ceilings "oasis" area and east elevator lobby as clouded and dated on approved plans. Discussed project schedule and hydro testing.
FIR13-00696 INSP-Final Inspection3/25/20143/25/20143/25/2014 11:14:28 AMAPART
Alarm and trouble conditions tested satisfactory. Final pending high pressure switch supervisory monitor.