Inspections for the day of: Wednesday, March 25, 2015.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00172 INSP-Final Inspection3/24/20153/25/20153/25/2015 5:07:16 PMPPASS
Hood suppression system operated correctly under test conditions. Permit finaled.
BLD15-00579 FIRE-Final Inspection3/25/20153/25/20153/25/2015 5:05:48 PMPPASS
Fire life safety inspection passed.
BLD14-01285 FIRE-Final Inspection3/24/20153/25/20153/25/2015 5:05:13 PMAPASS
Fire life safety inspection completed okay at the new addition per scope of work.
FIR14-00815 INSP-Sprinkler Rough-in3/25/20153/25/20153/25/2015 5:01:37 PMPPART
Area one 2nd floor soffits okayed for cover. Exceptions include missing sprinkler coverage at the concealed space electrical chase, sheetrock mud obstructing one upright sprinkler at a concealed space, three drops yet to be cut in at unit mechanical closets.
FIR15-00098 INSP-Final Inspection3/25/20153/25/20153/25/2015 4:56:24 PMPPASS
Fire sprinkler permit final approved.
FIR15-00133 INSP-Sprinkler Rough-in3/24/20153/25/20153/25/2015 4:54:10 PMAPART
Overhead rough-in approved for cover at the grid ceilings.