FIR15-00172
| INSP-Final Inspection | 3/24/2015 | 3/25/2015 | 3/25/2015 5:07:16 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions. Permit finaled.
|
BLD15-00579
| FIRE-Final Inspection | 3/25/2015 | 3/25/2015 | 3/25/2015 5:05:48 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
BLD14-01285
| FIRE-Final Inspection | 3/24/2015 | 3/25/2015 | 3/25/2015 5:05:13 PM | A | PASS |
|
|
Fire life safety inspection completed okay at the new addition per scope of work.
|
FIR14-00815
| INSP-Sprinkler Rough-in | 3/25/2015 | 3/25/2015 | 3/25/2015 5:01:37 PM | P | PART |
|
|
Area one 2nd floor soffits okayed for cover. Exceptions include missing sprinkler coverage at the concealed space electrical chase, sheetrock mud obstructing one upright sprinkler at a concealed space, three drops yet to be cut in at unit mechanical closets.
|
FIR15-00098
| INSP-Final Inspection | 3/25/2015 | 3/25/2015 | 3/25/2015 4:56:24 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR15-00133
| INSP-Sprinkler Rough-in | 3/24/2015 | 3/25/2015 | 3/25/2015 4:54:10 PM | A | PART |
|
|
Overhead rough-in approved for cover at the grid ceilings.
|