Inspections for the day of: Friday, March 25, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00905 INSP-Supply line flush3/25/20163/25/20163/25/2016 1:20:54 PMPPASS
The underground flush passed. Steve and I discussed the height of the FDC. I quoted the 4' max height in NFPA 13
FIR15-00710 INSP-Sprinkler Rough-in/Hydro3/23/20163/25/20163/25/2016 11:10:25 AMAPART
Sidewall sprinkler head added for the concealed space at the fireplace per the previous correction. Sprinkler protection is required in the master shower or an 8" lintel is to be provided to create a separate compartment. No tenting has been installed so no sprinkler piping is to be covered.
BLD15-03505 FIRE-Final Inspection3/24/20163/25/20163/25/2016 10:34:11 AMAPASS
life safety passed
BLD16-00197 FIRE-Final Inspection3/24/20163/25/20163/25/2016 8:01:58 AMAPASS
life safety passed. Only two narrow strips of foam matting and large plywood spring board was in the building.