Inspections for the day of: Monday, March 26, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00540 Permanent Service3/26/20073/26/20073/26/2007 3:57:29 PMPCANC
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see added r/i p/s
ELE07-00540 Rough-In Permanent Service3/26/20073/26/20073/26/2007 3:56:58 PMPFAIL
corr met contr, 300.4 nail plates and 11/4" 314.16 box fill, 334.30,314.17(C) staple romex 8"of boxes, 110.3(A) repair,replace damaged romex wall by back batjrm, 250.66T #4 to u/g water pipe, 250.24(A)(5) isolate grds neuts at subpanels,, 250.148 splice all equip grds at boxes, 300.15 shall install boxes at all outlets switch recepts, fixtures, BCC complete all makeup
ELE07-00970 Permanent Service3/26/20073/26/20073/26/2007 3:00:29 PMPPASS
isolate grds and neutrals at sub panel
p/s o/h rec, ok
ELE07-00970 Final3/26/20073/26/20073/26/2007 2:59:24 PMPPASS
ok
ELE07-00970 Final3/26/20073/26/20073/26/2007 2:13:04 PMPCANC
Wylie; Phone #: ###-#### Internet Inspection see added p/s
ELE07-00606 Final3/26/20073/26/20073/26/2007 2:10:35 PMPPASS
tom pls call first for access; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok card sign called reversed polarity recept down low by kit entry door
ELE07-00800 Temporary Service3/26/20073/26/20073/26/2007 1:46:53 PMPPASS
art - early as possible please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith t/s o/h new ok
ELE07-00858 Electrical Rough-In3/26/20073/26/20073/26/2007 1:24:16 PMACANC
Conduit only inspection in the east block wall. Thank you. Phone #: ###-#### see r/i added to permit # ele06-04666
ELE06-04666 Electrical Rough-In3/26/20073/26/20073/26/2007 1:22:30 PMPPART
wiring in block wall for lights ok
ELE06-03765 Electrical Rough-In3/23/20073/26/20073/26/2007 12:36:19 PMAPASS
casey - pls call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Victoria Beall needs plastic conn for grd wire and 2/0 copper or 4/0 alum from meter load side to line side p/s 200 amp main
ELE06-04690 Final3/26/20073/26/20073/26/2007 11:31:55 AMPPASS
cindy - on site in another building; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok no card
ELE07-00753 Rough-In Permanent Service3/23/20073/26/20073/26/2007 11:31:24 AMAPASS
On-site contact - Gene ###-#### Phone #: ###-#### r/i p/s u/g new ok
ELE07-00970 Permanent Service3/26/20073/26/20073/26/2007 10:34:54 AMANR
###-#### wylie needs listed r/t fittings, isolate geds and neutrals at subpanel
ELE07-00806 Final3/23/20073/26/20073/26/2007 10:00:13 AMAPASS
Phone #: ###-#### ok card signed
ELE06-04690 Final3/23/20073/26/20073/26/2007 9:36:12 AMANH
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
notice posted called no response
ELE06-04227 Final3/23/20073/26/20073/26/2007 9:19:37 AMAPASS
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
ELE07-00960 Electrical Rough-In3/24/20073/26/20073/26/2007 9:08:38 AMAPASS
Nail plates installed, wiring in first floor room verified, not connected to existing small appliance circuit. Phone #: ###-#### ok
ELE06-03281 Electrical Rough-In3/23/20073/26/20073/26/2007 8:42:16 AMAPART
Please inspect 3rd floor rough-in at A-wing. Thankyou. Phone #: ###-####
walls ceilings ok anop