ELE07-00540
| Permanent Service | 3/26/2007 | 3/26/2007 | 3/26/2007 3:57:29 PM | P | CANC |
|
|
jade; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see added r/i p/s
|
ELE07-00540
| Rough-In Permanent Service | 3/26/2007 | 3/26/2007 | 3/26/2007 3:56:58 PM | P | FAIL |
|
|
corr met contr, 300.4 nail plates and 11/4" 314.16 box fill, 334.30,314.17(C) staple romex 8"of boxes, 110.3(A) repair,replace damaged romex wall by back batjrm, 250.66T #4 to u/g water pipe, 250.24(A)(5) isolate grds neuts at subpanels,, 250.148 splice all equip grds at boxes, 300.15 shall install boxes at all outlets switch recepts, fixtures, BCC complete all makeup
|
ELE07-00970
| Permanent Service | 3/26/2007 | 3/26/2007 | 3/26/2007 3:00:29 PM | P | PASS |
|
|
isolate grds and neutrals at sub panel p/s o/h rec, ok
|
ELE07-00970
| Final | 3/26/2007 | 3/26/2007 | 3/26/2007 2:59:24 PM | P | PASS |
|
|
ok
|
ELE07-00970
| Final | 3/26/2007 | 3/26/2007 | 3/26/2007 2:13:04 PM | P | CANC |
|
|
Wylie; Phone #: ###-#### Internet Inspection see added p/s
|
ELE07-00606
| Final | 3/26/2007 | 3/26/2007 | 3/26/2007 2:10:35 PM | P | PASS |
|
|
tom pls call first for access; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok card sign called reversed polarity recept down low by kit entry door
|
ELE07-00800
| Temporary Service | 3/26/2007 | 3/26/2007 | 3/26/2007 1:46:53 PM | P | PASS |
|
|
art - early as possible please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith t/s o/h new ok
|
ELE07-00858
| Electrical Rough-In | 3/26/2007 | 3/26/2007 | 3/26/2007 1:24:16 PM | A | CANC |
|
|
Conduit only inspection in the east block wall. Thank you. Phone #: ###-#### see r/i added to permit # ele06-04666
|
ELE06-04666
| Electrical Rough-In | 3/26/2007 | 3/26/2007 | 3/26/2007 1:22:30 PM | P | PART |
|
|
wiring in block wall for lights ok
|
ELE06-03765
| Electrical Rough-In | 3/23/2007 | 3/26/2007 | 3/26/2007 12:36:19 PM | A | PASS |
|
|
casey - pls call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Victoria Beall needs plastic conn for grd wire and 2/0 copper or 4/0 alum from meter load side to line side p/s 200 amp main
|
ELE06-04690
| Final | 3/26/2007 | 3/26/2007 | 3/26/2007 11:31:55 AM | P | PASS |
|
|
cindy - on site in another building; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok no card
|
ELE07-00753
| Rough-In Permanent Service | 3/23/2007 | 3/26/2007 | 3/26/2007 11:31:24 AM | A | PASS |
|
|
On-site contact - Gene ###-#### Phone #: ###-#### r/i p/s u/g new ok
|
ELE07-00970
| Permanent Service | 3/26/2007 | 3/26/2007 | 3/26/2007 10:34:54 AM | A | NR |
|
|
###-#### wylie needs listed r/t fittings, isolate geds and neutrals at subpanel
|
ELE07-00806
| Final | 3/23/2007 | 3/26/2007 | 3/26/2007 10:00:13 AM | A | PASS |
|
|
Phone #: ###-#### ok card signed
|
ELE06-04690
| Final | 3/23/2007 | 3/26/2007 | 3/26/2007 9:36:12 AM | A | NH |
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus notice posted called no response
|
ELE06-04227
| Final | 3/23/2007 | 3/26/2007 | 3/26/2007 9:19:37 AM | A | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
|
ELE07-00960
| Electrical Rough-In | 3/24/2007 | 3/26/2007 | 3/26/2007 9:08:38 AM | A | PASS |
|
|
Nail plates installed, wiring in first floor room verified, not connected to existing small appliance circuit. Phone #: ###-#### ok
|
ELE06-03281
| Electrical Rough-In | 3/23/2007 | 3/26/2007 | 3/26/2007 8:42:16 AM | A | PART |
|
|
Please inspect 3rd floor rough-in at A-wing. Thankyou. Phone #: ###-#### walls ceilings ok anop
|