Inspections for the day of: Monday, March 26, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00881 Electrical Rough-In3/26/20073/26/20073/26/2007 4:35:33 PMPDONE
john - ditch for cover; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
the home owner is confused about where idaho power starts/stops, and where boise city begins. Talked with him and explained the difference.
ELE06-04658 Final3/26/20073/26/20073/26/2007 4:20:10 PMPPART
Scheduled by a contractor via Hello! on 3/26/2007 at 9:45:56 AM. Contact: ###-####.
1. only the feeder conduit, strapping at jbox in the back of the store needs to be looked at.
ELE07-00990 Conference3/26/20073/26/20073/26/2007 4:17:46 PMPDONE
Sean; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
talked about new mast, 8' clearence for structures, grounding, and sub panel locations.
ELE07-00990 Electrical Rough-In3/26/20073/26/20073/26/2007 4:04:57 PMPPASS
Sean; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
kitchen ri ok
ELE07-00587 Electrical Rough-In3/23/20073/26/20073/26/2007 2:49:20 PMAPASS
Underground conduit inspection Phone #: ###-####
ug conduit ok
ELE07-00987 Final3/26/20073/26/20073/26/2007 2:34:01 PMPPASS
final ok
ELE07-00987 Electrical Rough-In3/26/20073/26/20073/26/2007 2:32:42 PMPPASS
Brian; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
p/s u/g reconnect ok
ELE07-00959 Electrical Rough-In3/22/20073/26/20073/26/2007 2:12:25 PMAFAIL
Need wall cover & concrete floor inspection. Contact Karl Paige. Phone #: ###-####
358.30 & 330.30 emt/mc not fastened securley in place at boxes within the given parameters of each material.
ELE06-04152 Electrical Rough-In3/26/20073/26/20073/26/2007 1:14:17 PMPPASS
Rough-In Inspection WALLS ONLY Phone #: ###-####
1. hard lids in bathrooms and storage rm ok to cover.
2. stud walls throughout the building ok to cover
ELE07-00978 Electrical Rough-In3/23/20073/26/20073/26/2007 11:00:28 AMAPASS
Dino; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
ri ok
p/s u/g n ok
ELE07-00285 Final3/23/20073/26/20073/26/2007 10:41:40 AMAFAIL
Wayne Trench ; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
310.7 conductors shall be identified for direct burial.
110.3B manufacturers instructions-- trailer shall be fed with four wires to the panel
ELE07-00953 Electrical Rough-In3/22/20073/26/20073/26/2007 9:46:08 AMAFAIL
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
no bld permit
ELE07-00953 Electrical Rough-In3/26/20073/26/20073/26/2007 9:42:29 AMPFAIL
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
no building permit for this job, it needs one.
walls have been sheetrocked, and painted
ELE07-00983 Final3/23/20073/26/20073/26/2007 8:58:16 AMAFAIL
Underground conduit inspection for sign power @ Cricket Store. Phone #: ###-####
to shallow, and the entire length shall be uncovered for the inspection
ELE07-00185 Final3/23/20073/26/20073/26/2007 8:28:34 AMAPASS
please contact Patrick, thank you Phone #: ###-####
final ok