Inspections for the day of: Wednesday, March 26, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00112 INSP-Final Inspection3/25/20083/26/20083/26/2008 5:54:27 PMPFAIL
Noted four overspaced notification devices, two smoke detectors will need relocated, transponder panel has been moved from location shown on plans, battery trouble at the transponder is incorrectly descripted, speaker at one appliance at the cafeteria seating area is not operating correctly, noted cd ratings at various strobes are different from plan set, remainder of notification and initiation devices on the 4th floor tested acceptable, also tested kitchen hood alarm interconnection and freight elevator smoke guard door.
FIR07-00403 INSP-Alarm Testing3/26/20083/26/20083/26/2008 5:30:31 PMPNR
Work is not completed for inspection.
BLD08-00361 FIRE-Final Inspection3/26/20083/26/20083/26/2008 5:29:30 PMPPASS
Fire life safety passed, the supervisory at the main FACP cleared while on site-sprinkler tamper.
BLD06-02260 FIRE-Final Inspection3/26/20083/26/20083/26/2008 2:25:10 PMPCANC
Per permit documents and scope of work, no fire related signatures are required. Contacted permit holder to discuss. Inspection canceled.
FIR07-00917 INSP-Final Inspection3/25/20083/26/20083/26/2008 1:18:28 PMANR
Permit cannot be finaled at this time due to missing ceiling tiles at several locations including the relocated head spaces. Noted work is underway and ceilings will be completed by the end of day per general contractor. Can verify completion and final permit in conjunction with the building life safety inspection as discussed.
FIR07-00880 INSP-Final Inspection3/25/20083/26/20083/26/2008 12:50:01 PMAFAIL
Prior to inspection the NFPA 72 "Inspection and testing" form Fig. 10.6.2.3 must be completed including a copy of the supervising station signals report- see fire code review notes #8, audible notification at the existing tenant URS is not temporal as required, provide key for elevator reset at the next inspection. Manual pull, SD at the panel, sprinkler monitoring, FACP phone lines, batteries, AC loss, and the duct detector tested okay, notification device locations for the first and second floors appear satisfactory. Elevator controls not tested at this tme.
FIR06-00365 INSP-Final Inspection3/26/20083/26/20083/26/2008 11:32:58 AMAPASS
Noted corrections are complete, fire sprinkler permit finaled.
BLD07-02883 FIRE-Final Inspection3/26/20083/26/20083/26/2008 11:16:20 AMAPASS
Fire life safety is acceptable pending address numbers and max. occupant load sign are posted today as agreed and completed prior to structural final.