Inspections for the day of: Thursday, March 26, 2009.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00614 FIR-Aging Inspection3/26/20093/26/20093/27/2009 8:08:40 PMPDONE
Okay for void or final as project related OH permit has been voided and subsequent permit for same scope of work has been finaled.
BLD09-00239 FIRE-Final Inspection3/26/20093/26/20093/27/2009 8:05:52 AMPFAIL
Need to post 2A10BC and K class fire extinguishers as discussed, provide approved hardware at the restroom door-see anntoations on plans.
FIR08-00480 INSP-Final Inspection3/25/20093/26/20093/27/2009 8:03:12 AMAFAIL
Noted two locations where sprinkler heads are blocked by adjacent light fixtures including the studio storage room 1st floor and a basement closet, missing sheetrock ceilings at basement rooms south side. Flow testing completed.
FIR09-00152 INSP-Final Inspection3/26/20093/26/20093/27/2009 7:51:51 AMPPASS
C/N issues completed, fire alarm retest passed, pemit finaled.
BLD08-02567 FIRE-Final Inspection3/26/20093/26/20093/27/2009 7:50:44 AMPPASS
Noted correction items verified for completion, fire life safety finaled.
FIR08-00797 INSP-Final Inspection3/26/20093/26/20093/27/2009 7:49:32 AMPPASS
Fire sprinkler permit work approved for final.
FIR09-00178 INSP-Final Inspection3/25/20093/26/20093/27/2009 7:48:29 AMPPASS
Hood suppression system functioned properly under test conditions.
FIR08-00766 INSP-Sprinkler Rough-in/Hydro3/26/20093/26/20093/27/2009 7:47:27 AMPPART
UG fire supply line hydrostatic test for the east half of the building service passed- see marked area on approved plan set.
FIR08-00480 INSP-Supply line flush3/26/20093/26/20093/26/2009 12:28:23 PMAPART
Supply line flush completed per activity notes 8/12.
FIR08-00828 INSP-Final Inspection3/24/20093/26/20093/26/2009 12:26:34 PMAPASS
Fire alarm testing completed satisfactory, address changes at SD okayed, as-built for 4wire notification devices is acceptable, permit finaled.
BLD07-02391 FIRE-Final Inspection3/26/20093/26/20093/26/2009 12:24:10 PMAPASS
Fire life safety approved, see inspection comments 6/18.
FIR08-00433 INSP-Final Inspection3/26/20093/26/20093/26/2009 12:22:36 PMAPASS
Fire sprinkler permit finaled.