FIR04-00614
| FIR-Aging Inspection | 3/26/2009 | 3/26/2009 | 3/27/2009 8:08:40 PM | P | DONE |
|
|
Okay for void or final as project related OH permit has been voided and subsequent permit for same scope of work has been finaled.
|
BLD09-00239
| FIRE-Final Inspection | 3/26/2009 | 3/26/2009 | 3/27/2009 8:05:52 AM | P | FAIL |
|
|
Need to post 2A10BC and K class fire extinguishers as discussed, provide approved hardware at the restroom door-see anntoations on plans.
|
FIR08-00480
| INSP-Final Inspection | 3/25/2009 | 3/26/2009 | 3/27/2009 8:03:12 AM | A | FAIL |
|
|
Noted two locations where sprinkler heads are blocked by adjacent light fixtures including the studio storage room 1st floor and a basement closet, missing sheetrock ceilings at basement rooms south side. Flow testing completed.
|
FIR09-00152
| INSP-Final Inspection | 3/26/2009 | 3/26/2009 | 3/27/2009 7:51:51 AM | P | PASS |
|
|
C/N issues completed, fire alarm retest passed, pemit finaled.
|
BLD08-02567
| FIRE-Final Inspection | 3/26/2009 | 3/26/2009 | 3/27/2009 7:50:44 AM | P | PASS |
|
|
Noted correction items verified for completion, fire life safety finaled.
|
FIR08-00797
| INSP-Final Inspection | 3/26/2009 | 3/26/2009 | 3/27/2009 7:49:32 AM | P | PASS |
|
|
Fire sprinkler permit work approved for final.
|
FIR09-00178
| INSP-Final Inspection | 3/25/2009 | 3/26/2009 | 3/27/2009 7:48:29 AM | P | PASS |
|
|
Hood suppression system functioned properly under test conditions.
|
FIR08-00766
| INSP-Sprinkler Rough-in/Hydro | 3/26/2009 | 3/26/2009 | 3/27/2009 7:47:27 AM | P | PART |
|
|
UG fire supply line hydrostatic test for the east half of the building service passed- see marked area on approved plan set.
|
FIR08-00480
| INSP-Supply line flush | 3/26/2009 | 3/26/2009 | 3/26/2009 12:28:23 PM | A | PART |
|
|
Supply line flush completed per activity notes 8/12.
|
FIR08-00828
| INSP-Final Inspection | 3/24/2009 | 3/26/2009 | 3/26/2009 12:26:34 PM | A | PASS |
|
|
Fire alarm testing completed satisfactory, address changes at SD okayed, as-built for 4wire notification devices is acceptable, permit finaled.
|
BLD07-02391
| FIRE-Final Inspection | 3/26/2009 | 3/26/2009 | 3/26/2009 12:24:10 PM | A | PASS |
|
|
Fire life safety approved, see inspection comments 6/18.
|
FIR08-00433
| INSP-Final Inspection | 3/26/2009 | 3/26/2009 | 3/26/2009 12:22:36 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|