Inspections for the day of: Thursday, March 26, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00584 INSP-Final Inspection3/25/20093/26/20093/27/2009 12:49:10 PMPPASS
Permit finaled
FIR09-00181 INSP-Final Inspection3/26/20093/26/20093/26/2009 4:06:04 PMPPASS
permit finaled
FIR09-00029 INSP-Final Inspection3/26/20093/26/20093/26/2009 3:02:58 PMPPASS
permit finaled
BLD08-02552 FIRE-Final Inspection3/26/20093/26/20093/26/2009 2:22:27 PMPFAIL
Life safety will be ok to final when the project related fire alarm permti is finaled
FIR09-00116 INSP-Final Inspection3/25/20093/26/20093/26/2009 2:14:21 PMPFAIL
The duct smoke detector located over the office area is mounted incorrectly which has been verified with FireX technical support. An updated map is also required at the facp. The plans also indicated existing duct smoke detectors in other tenant spaces. These detectors are not connected to the existing fire alarm panel as required by the IMC. I contacted Mark Senteno with the fire dept. via email about this issue.
FIR09-00146 INSP-Final Inspection3/25/20093/26/20093/26/2009 1:26:39 PMAFAIL
Not ready for a final due to dry system hydro test failure.
FIR09-00146 INSP-Sprinkler Rough-in/Hydro3/25/20093/26/20093/26/2009 1:26:08 PMAPART
The sprinkler head change out passed. The hydro test for the wet system passed. The hydro test for the dry system failed due to a leaking 4" main.
BLD08-01664 FIRE-Final Inspection3/23/20093/26/20093/26/2009 10:51:25 AMAFAIL
The project related fire alarm and fire sprinkler permits need to be finaled. Also panic hardware is required to be installed on the conference room door, provide additional emergency lighting in the two adjoining main north facing lobbys. Provide non-locking hardware from the warehouse due to an exit sign over the door or get plan reviewer permission to delete the exit sign. Provide single action hardware on the south exit door from the warehouse.
FIR08-00778 INSP-Sprinkler Rough-in/Hydro3/25/20093/26/20093/26/2009 10:48:11 AMAPASS
All items have been corrected except the interconnection/operation of the pre-action system.