Inspections for the day of: Friday, March 26, 2010.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00536 INSP-Sprinkler Rough-in3/26/20103/26/20103/26/2010 5:43:04 PMPPART
See clouded areas marked on stamped plan set at the second floor level classrooms okayed for ceiling cover- Includes rough-in and final head locations. Classroom 202 at the south end is not approved for cover due to exposed combustible construction above the drop ceiling lacking protection. Seismic brace locations at the feed mains in the basement riser room are acceptable.
FIR06-00898 INSP-Final Inspection3/26/20103/26/20103/26/2010 5:32:47 PMPPASS
Fire sprinkler permit work okay for final status, project completed. Final inspections passed.
FIR06-00898 INSP-Conference3/26/20103/26/20103/26/2010 5:31:16 PMPDONE
FIR05-00787 INSP-Final Inspection3/26/20103/26/20103/26/2010 5:30:45 PMPPASS
Underground fire supply line permit final approved.
FIR05-00787 INSP-Conference3/26/20103/26/20103/26/2010 5:29:51 PMPDONE
Regarding permit status and conditions on parcel hold for this address.
BLD09-00101 FIRE-Final Inspection3/26/20103/26/20103/26/2010 5:28:55 PMPPASS
Life safety finaled, inspection passed.
BLD09-01336 FIRE-Final Inspection3/25/20103/26/20103/26/2010 5:28:00 PMAPASS
Life safety inspection completed satisfactory. Noted some site work incomplete. Existing hydrant locations approved per M. Sentenno- see plan review comments.
BLD10-00368 FIRE-Final Inspection3/26/20103/26/20103/26/2010 5:23:57 PMAPART
ref. NFPA 80 regarding min. and max closure rate for the relocated fire door- (6"/sec. - 24"/sec.).
FIR09-00540 INSP-Sprinkler Rough-in/Hydro3/25/20103/26/20103/26/2010 5:18:43 PMAPART
Remote FDC piping hydrostatic test completed satisfactory.
BLD08-01553 FIRE-Final Inspection3/26/20103/26/20103/26/2010 3:44:11 PMAPASS
Correction item site verified for completion, fire life safety finaled. Notified structural inspector of project status change.