FIR12-00119
| INSP-Final Inspection | 3/23/2012 | 3/26/2012 | 3/26/2012 3:22:03 PM | A | FAIL |
|
|
The alarm tech and I could not get access into the project. No inspection was performed.
|
FIR09-00094
| INSP-Final Inspection | 3/26/2012 | 3/26/2012 | 3/26/2012 3:14:39 PM | P | PASS |
|
|
permit finaled
|
FIR12-00139
| INSP-Sprinkler Rough-in | 3/23/2012 | 3/26/2012 | 3/26/2012 11:57:41 AM | A | CANC |
|
|
Per Jeff the stamped set of "to remain on job site" plans are not on the job site. I let him know I need these for the inspection. I contacted Jeff Packham in the office to see if some one could meet me there with them but that was not possible either. No inspection was performed.
|
FIR09-00094
| INSP-Final Inspection | 3/26/2012 | 3/26/2012 | 3/26/2012 10:23:19 AM | A | FAIL |
|
|
An Intella-tap is installed but not shown on the approved plans. The relay for the antenna trouble did not activate. Per alarm tech. these items will be addressed and I agreed to re-inspect this afternoon.
|
FIR09-00079
| INSP-Final Inspection | 3/23/2012 | 3/26/2012 | 3/26/2012 10:20:48 AM | A | PASS |
|
|
Permit finaled
|