Inspections for the day of: Tuesday, March 26, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00668 Electrical Rough-In3/26/20133/26/20133/26/2013 2:54:22 PMPFAIL
Installed power to AC and gas furnace in suite A. Someone will be there all day. Please final. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Over current protection for outdoor unit exceeds maximum, Sealtite flex requires strap, A/C outdoor unit requires service receptacle within 25 ft.
ELE13-00580 Electrical Rough-In3/26/20133/26/20133/26/2013 2:06:05 PMPPASS
enrique Phone #: ###-#### - call 30 mins prior r/i ok cover
ELE13-00694 Permanent Service3/26/20133/26/20133/26/2013 1:34:37 PMPFAIL
Robert Phone #: ###-#### NEC 250.56 permanenet service requires two grounding electrodes six feet apart with eight feet in contact with the earth. Fifty amp Cutler Hammer breaker not listed for two conductors per lug.
ELE12-02630 Permanent Service3/26/20133/26/20133/26/2013 1:02:11 PMPNR
Contact is Ben MacDonagh Phone #: ###-#### >> Inspection requested via web by Scott Campbell Not ready wrong job called for inspection
ELE13-00360 Final3/26/20133/26/20133/26/2013 12:31:10 PMPPART
Lynn Phone #: ###-#### Partial final
ELE13-00698 Electrical Rough-In3/25/20133/26/20133/26/2013 10:02:15 AMAPASS
wall inspect call corey with questions thanks
Phone #: ###-#### >> Inspection requested via web by Don Lustig rough-in ok cover walls
ELE10-02007 Final3/26/20133/26/20133/26/2013 9:43:22 AMAPASS
Job complete,correction done final ok
ELE13-00451 Final3/25/20133/26/20133/26/2013 9:31:58 AMAPASS
Car wash on west side of building. Call my cell at ###-#### if you have any questions. Thanks, Paul White Phone #: ###-#### >> Inspection requested via web by Paul White UL listed equipment final ok
ELE13-00677 Electrical Rough-In3/26/20133/26/20133/26/2013 9:17:10 AMAPASS
Rough-in ok cover No permanent service
ELE13-00677 Rough-In Permanent Service3/25/20133/26/20133/26/2013 9:16:36 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Robert Murray NEC 310.15(B)(2) Conductor adjustment factor-more than 3 current carring conductors in a raceway or cable.
ELE13-00544 Final3/25/20133/26/20133/26/2013 8:45:02 AMAPASS
home from 8:00-12:00 am Phone #: ###-#### >> Inspection requested via web by Jesse Fuentes final ok
ELE13-00694 Permanent Service3/25/20133/26/20133/26/2013 8:16:00 AMANH
Robert Phone #: ###-#### No access
ELE12-02941 Final3/25/20133/26/20133/26/2013 8:03:24 AMAPASS
luke Phone #: ###-#### final ok