ELE13-00668
| Electrical Rough-In | 3/26/2013 | 3/26/2013 | 3/26/2013 2:54:22 PM | P | FAIL |
|
|
Installed power to AC and gas furnace in suite A. Someone will be there all day. Please final. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Over current protection for outdoor unit exceeds maximum, Sealtite flex requires strap, A/C outdoor unit requires service receptacle within 25 ft.
|
ELE13-00580
| Electrical Rough-In | 3/26/2013 | 3/26/2013 | 3/26/2013 2:06:05 PM | P | PASS |
|
|
enrique Phone #: ###-#### - call 30 mins prior r/i ok cover
|
ELE13-00694
| Permanent Service | 3/26/2013 | 3/26/2013 | 3/26/2013 1:34:37 PM | P | FAIL |
|
|
Robert Phone #: ###-#### NEC 250.56 permanenet service requires two grounding electrodes six feet apart with eight feet in contact with the earth. Fifty amp Cutler Hammer breaker not listed for two conductors per lug.
|
ELE12-02630
| Permanent Service | 3/26/2013 | 3/26/2013 | 3/26/2013 1:02:11 PM | P | NR |
|
|
Contact is Ben MacDonagh Phone #: ###-#### >> Inspection requested via web by Scott Campbell Not ready wrong job called for inspection
|
ELE13-00360
| Final | 3/26/2013 | 3/26/2013 | 3/26/2013 12:31:10 PM | P | PART |
|
|
Lynn Phone #: ###-#### Partial final
|
ELE13-00698
| Electrical Rough-In | 3/25/2013 | 3/26/2013 | 3/26/2013 10:02:15 AM | A | PASS |
|
|
wall inspect call corey with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig rough-in ok cover walls
|
ELE10-02007
| Final | 3/26/2013 | 3/26/2013 | 3/26/2013 9:43:22 AM | A | PASS |
|
|
Job complete,correction done final ok
|
ELE13-00451
| Final | 3/25/2013 | 3/26/2013 | 3/26/2013 9:31:58 AM | A | PASS |
|
|
Car wash on west side of building. Call my cell at ###-#### if you have any questions. Thanks, Paul White Phone #: ###-#### >> Inspection requested via web by Paul White UL listed equipment final ok
|
ELE13-00677
| Electrical Rough-In | 3/26/2013 | 3/26/2013 | 3/26/2013 9:17:10 AM | A | PASS |
|
|
Rough-in ok cover No permanent service
|
ELE13-00677
| Rough-In Permanent Service | 3/25/2013 | 3/26/2013 | 3/26/2013 9:16:36 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Murray NEC 310.15(B)(2) Conductor adjustment factor-more than 3 current carring conductors in a raceway or cable.
|
ELE13-00544
| Final | 3/25/2013 | 3/26/2013 | 3/26/2013 8:45:02 AM | A | PASS |
|
|
home from 8:00-12:00 am Phone #: ###-#### >> Inspection requested via web by Jesse Fuentes final ok
|
ELE13-00694
| Permanent Service | 3/25/2013 | 3/26/2013 | 3/26/2013 8:16:00 AM | A | NH |
|
|
Robert Phone #: ###-#### No access
|
ELE12-02941
| Final | 3/25/2013 | 3/26/2013 | 3/26/2013 8:03:24 AM | A | PASS |
|
|
luke Phone #: ###-#### final ok
|