ELE12-01902
| ELE-Aging Inspection | 3/26/2014 | 3/26/2014 | 4/1/2014 4:40:50 PM | | DONE |
|
|
Called, contractor will check job for access and schedule
|
ELE12-01900
| ELE-Aging Inspection | 3/26/2014 | 3/26/2014 | 4/1/2014 4:34:11 PM | | DONE |
|
|
Called, contractor will check job for access and schedule
|
ELE14-00485
| Final | 3/26/2014 | 3/26/2014 | 3/26/2014 2:56:00 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot 230.62- Energized live parts of service equiptment shall be enclosed. Install cover. 408.4- Service circuit dirctory shall be completed. 314.25- Box by water heater shall have cover 210.63- A 125 v, 15 or 20 amp receptical outlet shall be installed with in 25' of AC equiptment.
|
ELE14-00729
| Electrical Rough-In | 3/26/2014 | 3/26/2014 | 3/26/2014 2:06:47 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt Addition rough in ok cover
|
ELE14-00729
| Permanent Service | 3/26/2014 | 3/26/2014 | 3/26/2014 1:39:54 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt p/s o/h rec ok
|
ELE13-00892
| Final | 3/26/2014 | 3/26/2014 | 3/26/2014 1:26:00 PM | P | FAIL |
|
|
clay Phone #: ###-#### 410.16(C)- Incandecent luminaire minimum clearence from shelf of 12" shall be met.
|
ELE14-00728
| Temporary Service | 3/26/2014 | 3/26/2014 | 3/26/2014 12:46:41 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey t/s u/g n ok
|
ELE14-00672
| Electrical Rough-In | 3/26/2014 | 3/26/2014 | 3/26/2014 9:42:39 AM | A | PART |
|
|
Rock
I want the exercise room and the bath of room 119. I will do the hallway when we do the next insp. the contractor has contacted the LV guys to clean up the wires.
Thanks
Mike Cole Phone #: ###-#### >> Inspection requested via web by Mike Cole Exersize and bathroom for room 119 rough in ok cover
|
ELE14-00319
| Electrical Rough-In | 3/25/2014 | 3/26/2014 | 3/26/2014 9:16:48 AM | A | PART |
|
|
Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson 2 exam rooms and offices N.E. corner as noted on print and high lighted. wall rough in ok cover
|
ELE14-00644
| Final | 3/25/2014 | 3/26/2014 | 3/26/2014 8:38:37 AM | A | CANC |
|
|
Contact person is Jim Snodgrass. Phone #: ###-#### >> Inspection requested via web by Todd Sellman Needed permanent service
|
ELE14-00644
| Permanent Service | 3/26/2014 | 3/26/2014 | 3/26/2014 8:38:18 AM | P | PASS |
|
|
Contact person is Jim Snodgrass. Phone #: ###-#### >> Inspection requested via web by Todd Sellman p/s u/g n ok
|