Inspections for the day of: Wednesday, March 26, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01902 ELE-Aging Inspection3/26/20143/26/20144/1/2014 4:40:50 PM DONE
Called, contractor will check job for access and schedule
ELE12-01900 ELE-Aging Inspection3/26/20143/26/20144/1/2014 4:34:11 PM DONE
Called, contractor will check job for access and schedule
ELE14-00485 Final3/26/20143/26/20143/26/2014 2:56:00 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot
230.62- Energized live parts of service equiptment shall be enclosed. Install cover.
408.4- Service circuit dirctory shall be completed.
314.25- Box by water heater shall have cover
210.63- A 125 v, 15 or 20 amp receptical outlet shall be installed with in 25' of AC equiptment.
ELE14-00729 Electrical Rough-In3/26/20143/26/20143/26/2014 2:06:47 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt Addition rough in ok cover
ELE14-00729 Permanent Service3/26/20143/26/20143/26/2014 1:39:54 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt
p/s o/h rec ok
ELE13-00892 Final3/26/20143/26/20143/26/2014 1:26:00 PMPFAIL
clay Phone #: ###-####
410.16(C)- Incandecent luminaire minimum clearence from shelf of 12" shall be met.
ELE14-00728 Temporary Service3/26/20143/26/20143/26/2014 12:46:41 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey t/s u/g n ok
ELE14-00672 Electrical Rough-In3/26/20143/26/20143/26/2014 9:42:39 AMAPART
Rock

I want the exercise room and the bath of room 119. I will do the hallway when we do the next insp. the contractor has contacted the LV guys to clean up the wires.

Thanks

Mike Cole Phone #: ###-#### >> Inspection requested via web by Mike Cole
Exersize and bathroom for room 119 rough in ok cover
ELE14-00319 Electrical Rough-In3/25/20143/26/20143/26/2014 9:16:48 AMAPART
Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson
2 exam rooms and offices N.E. corner as noted on print and high lighted. wall rough in ok cover
ELE14-00644 Final3/25/20143/26/20143/26/2014 8:38:37 AMACANC
Contact person is Jim Snodgrass. Phone #: ###-#### >> Inspection requested via web by Todd Sellman Needed permanent service
ELE14-00644 Permanent Service3/26/20143/26/20143/26/2014 8:38:18 AMPPASS
Contact person is Jim Snodgrass. Phone #: ###-#### >> Inspection requested via web by Todd Sellman p/s u/g n ok