ELE12-01902
| ELE-Aging Inspection | 3/26/2015 | 3/26/2015 | 3/27/2015 10:32:15 AM | | DONE |
|
|
Witing on owner
|
ELE15-00790
| Permanent Service | 3/26/2015 | 3/26/2015 | 3/26/2015 3:57:40 PM | P | PASS |
|
|
Pedestal panel at the North East corner of the property needs inspected. Contact Chris for questions at ###-####. Phone #: ###-#### Inspection requested via web by Lori Stout Will check second ground rod at future inspection. p/s u/g n ok
|
ELE15-00039
| Final | 3/26/2015 | 3/26/2015 | 3/26/2015 3:21:28 PM | P | PASS |
|
|
code 5151 enter Phone #: ###-#### Inspection requested via web by ron spen cer Final ok
|
ELE15-00126
| Final | 3/26/2015 | 3/26/2015 | 3/26/2015 3:04:55 PM | P | FAIL |
|
|
code 5151enter Phone #: ###-#### Inspection requested via web by ron spen cer 210.12- All 15 and 20 amp 120 volt outlets shall have AFCI protection. Master and smokes. 408.4- Master bed miss labeled. 110.3 Washer receptacle reverse polarity. 210.8- All 120 volt recetacles located with in 6' of sink shall have GFCI protection. Back sid of kit sink.
|
ELE15-00743
| Electrical Rough-In | 3/26/2015 | 3/26/2015 | 3/26/2015 2:39:46 PM | P | PASS |
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson Rough in ok cover
|
ELE15-00743
| Permanent Service | 3/26/2015 | 3/26/2015 | 3/26/2015 2:23:35 PM | P | PASS |
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson p/s u/g n ok
|
ELE15-00451
| Final | 3/26/2015 | 3/26/2015 | 3/26/2015 12:21:18 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
ELE14-03385
| Final | 3/25/2015 | 3/26/2015 | 3/26/2015 10:38:20 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton All ok need to inspect 2 conference tables for UL listing and connection. Temp final ok
|
ELE15-00456
| Final | 3/25/2015 | 3/26/2015 | 3/26/2015 9:45:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher UL listing confirmed Final ok
|
ELE15-00568
| Rough-In Permanent Service | 3/25/2015 | 3/26/2015 | 3/26/2015 9:27:34 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas Rough in ok cover p/s u/g n ok
|
ELE15-00569
| Rough-In Permanent Service | 3/25/2015 | 3/26/2015 | 3/26/2015 9:12:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas Rough in ok cover p/s u/g n ok
|
ELE15-00713
| Rough-In Permanent Service | 3/25/2015 | 3/26/2015 | 3/26/2015 8:32:27 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|