FIR15-00054
| INSP-Sprinkler Rough-in | 3/25/2015 | 3/26/2015 | 3/26/2015 3:46:44 PM | P | PASS |
|
|
Piping ok to cover at the Bakery soffits
|
FIR14-00914
| INSP-Final Inspection | 3/26/2015 | 3/26/2015 | 3/26/2015 3:45:29 PM | P | CANC |
|
|
Overbooked.
|
FIR15-00105
| INSP-Final Inspection | 3/23/2015 | 3/26/2015 | 3/26/2015 3:38:03 PM | P | FAIL |
|
|
Fire pump certification and flow test with factory rep. passed as witnessed by Tim Frost. Still need to verify connections to the FACP.
|
FIR15-00150
| INSP-Alarm Testing | 3/23/2015 | 3/26/2015 | 3/26/2015 3:37:29 PM | P | FAIL |
|
|
Plans need to be re-submitted showing the additional notification devices needed and relocated NAC panels and NAC panel triggers. Several strobes are overspaced. Alot of old devices have not been removed. Strobes need to be added in common restrooms and Linen Rooms/Laundery Rooms. There are ceiling obstructions that effect strobe placement and smoke detector placement.
|
FIR15-00124
| INSP-Sprinkler Rough-in/Hydro | 3/25/2015 | 3/26/2015 | 3/26/2015 3:24:36 PM | P | FAIL |
|
|
Hood suppression system functioned correctly but registered at the fire alarm panel as a supervisory signal. Must be alarm sigal.
|
FIR14-00872
| INSP-Sprinkler Rough-in/Hydro | 3/25/2015 | 3/26/2015 | 3/26/2015 1:10:10 PM | A | PART |
|
|
Underground flush passed, overhead hydro failed & only the rough-in in the west tenant passed. Will need as-builts showing the additional branchline and changes.
|
BLD14-02708
| FIRE-Final Inspection | 3/25/2015 | 3/26/2015 | 3/26/2015 12:35:07 PM | A | PASS |
|
|
Life safety passed
|
BLD15-00825
| FIRE-Final Inspection | 3/25/2015 | 3/26/2015 | 3/26/2015 10:20:24 AM | A | FAIL |
|
|
Relocate smoke alarm to 3' minimum from the restroom door, smoke alarms shall all activate when one activates, mount fire extinguisher as discussed
|
FIR14-00602
| INSP-Final Inspection | 3/24/2015 | 3/26/2015 | 3/24/2015 2:36:16 PM | A | CANC |
|
|
Mike S is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|