Inspections for the day of: Thursday, March 26, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00054 INSP-Sprinkler Rough-in3/25/20153/26/20153/26/2015 3:46:44 PMPPASS
Piping ok to cover at the Bakery soffits
FIR14-00914 INSP-Final Inspection3/26/20153/26/20153/26/2015 3:45:29 PMPCANC
Overbooked.
FIR15-00105 INSP-Final Inspection3/23/20153/26/20153/26/2015 3:38:03 PMPFAIL
Fire pump certification and flow test with factory rep. passed as witnessed by Tim Frost. Still need to verify connections to the FACP.
FIR15-00150 INSP-Alarm Testing3/23/20153/26/20153/26/2015 3:37:29 PMPFAIL
Plans need to be re-submitted showing the additional notification devices needed and relocated NAC panels and NAC panel triggers. Several strobes are overspaced. Alot of old devices have not been removed. Strobes need to be added in common restrooms and Linen Rooms/Laundery Rooms. There are ceiling obstructions that effect strobe placement and smoke detector placement.
FIR15-00124 INSP-Sprinkler Rough-in/Hydro3/25/20153/26/20153/26/2015 3:24:36 PMPFAIL
Hood suppression system functioned correctly but registered at the fire alarm panel as a supervisory signal. Must be alarm sigal.
FIR14-00872 INSP-Sprinkler Rough-in/Hydro3/25/20153/26/20153/26/2015 1:10:10 PMAPART
Underground flush passed, overhead hydro failed & only the rough-in in the west tenant passed. Will need as-builts showing the additional branchline and changes.
BLD14-02708 FIRE-Final Inspection3/25/20153/26/20153/26/2015 12:35:07 PMAPASS
Life safety passed
BLD15-00825 FIRE-Final Inspection3/25/20153/26/20153/26/2015 10:20:24 AMAFAIL
Relocate smoke alarm to 3' minimum from the restroom door, smoke alarms shall all activate when one activates, mount fire extinguisher as discussed
FIR14-00602 INSP-Final Inspection3/24/20153/26/20153/24/2015 2:36:16 PMACANC
Mike S is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus