Inspections for the day of: Thursday, March 26, 2020.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-01232 Pressure Test3/26/20203/26/20203/26/2020 4:10:38 PMPPASS
Can you call Tom, if there are any issues Phone #: ###-#### Inspection requested via web by Nat Golden
- 20lb gas pressure test ok
- tagged meter location
MEC20-01229 Pressure Test3/26/20203/26/20203/26/2020 4:09:14 PMPPASS
Can you call Tom, if there are any issues Phone #: ###-#### Inspection requested via web by Nat Golden
- 20lb gas pressure test ok
- tagged meter location
MEC20-01155 Rough-in3/26/20203/26/20203/26/2020 2:40:53 PMPPASS
Inspection requested via web by jeff jedlick
- R/I ok
MEC20-01156 Rough-in3/26/20203/26/20203/26/2020 2:40:38 PMPPASS
I will be there Phone #: ###-#### Inspection requested via web by jeff jedlick
- R/I ok
MEC20-01155 Pressure Test3/26/20203/26/20203/26/2020 2:40:25 PMPPASS
Inspection requested via web by jeff jedlick
- 5lb flue pressure test ok
- 20lb gas pressure test ok
- tagged meter location
MEC20-01156 Pressure Test3/26/20203/26/20203/26/2020 2:38:09 PMPPASS
I will be there Phone #: ###-#### Inspection requested via web by jeff jedlick
- 5lb flue pressure test
- 20lb gas pressure test ok
- tagged meter location
MEC20-01175 Final3/26/20203/26/20203/26/2020 2:05:47 PMPPASS
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace ac coil co ok
MEC20-01206 Final3/26/20203/26/20203/26/2020 1:27:17 PMPPASS
Teresa Greene ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace only co ok
MEC20-01109 Final3/23/20203/26/20203/26/2020 1:03:03 PMPPASS
###-#### Brian Gordon-Manager is meeting you there. He needs 20 mins heads-up.
80% Furnace replacement. Carbon monoxide detector in place. Phone #: ###-#### Inspection requested via web by Brian Preece
- furnace only co ok
MEC20-01216 Rough-in3/23/20203/26/20203/26/2020 11:47:24 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- gas line penetration needs protective coating
- duct connections at exhaust fans need sealed
- line set insulation in attic needs repaired
MEC20-01216 Pressure Test3/23/20203/26/20203/26/2020 11:45:13 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 20lb gas pressure test ok
- tagged meter location
MEC20-01237 Pressure Test3/24/20203/26/20203/26/2020 9:58:15 AMAPASS
Please call doran prior to arriving so he can gain you access.

thanks
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- 60lb gas pressure test ok
- tagged meter location
MEC20-00116 Final3/25/20203/26/20203/26/2020 9:16:32 AMANR
Call for access // peter Phone #: ###-####
- work is not complete
- finish work then schedule final inspection
MEC19-05241 Rough-in3/25/20203/26/20203/26/2020 8:49:59 AMAPASS
1st Floor Grid
Please contact Jesse prior to arrival
###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- 1st floor R/I ceiling cover ok
MEC19-03912 Mec-Aging Inspection3/26/20203/26/20203/26/2020 8:27:12 AM PASS
Doc Permit Finaled ok
MEC19-03912 DOC - Permit Finaled3/26/20203/26/20203/26/2020 8:26:54 AMAPASS
Doc Permit Finaled ok
MEC19-03928 Mec-Aging Inspection3/26/20203/26/20203/26/2020 8:26:11 AM FAIL
Permit has not been active since a no access on 9-12-19. Schedule inspection with homeowner if work is finished.