ELE06-00058
| Electrical Rough-In | 3/27/2006 | 3/27/2006 | 3/27/2006 4:17:10 PM | P | PART |
|
|
contact: chris carmine underground/roughin inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy u/g at BC lot, UPS systems at parking garage
|
ELE06-00986
| Permanent Service | 3/27/2006 | 3/27/2006 | 3/27/2006 3:17:25 PM | P | PASS |
|
|
leslie -call 1st before insp -late pm if possible; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie p/s o/h rec. ok
|
ELE05-03919
| Permanent Service | 3/23/2006 | 3/27/2006 | 3/27/2006 2:29:45 PM | P | PASS |
|
|
PLEASE CALL DAVE BRADSHAW TO MEET INSPECTOR ON SITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail r/i for new subpanel ok
|
ELE06-01024
| Rough-In Permanent Service | 3/27/2006 | 3/27/2006 | 3/27/2006 1:26:47 PM | P | PASS |
|
|
rick ###-#### r/i p/s u/g new ok
|
ELE05-04579
| Final | 3/24/2006 | 3/27/2006 | 3/27/2006 12:42:35 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/24/2006 at 5:23:07 PM. Contact: ###-####. ok
|
ELE06-01023
| Temporary Service | 3/26/2006 | 3/27/2006 | 3/27/2006 12:17:01 PM | A | FAIL |
|
|
charlie Internet Inspection Request from: Melyne Davis called no address, no sticker , told contractor before addresses shall be posted on yellow card
|
ELE05-02847
| Final | 3/24/2006 | 3/27/2006 | 3/27/2006 11:45:14 AM | A | NH |
|
|
butch ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie no access wet concrete called
|
ELE06-00856
| Electrical Rough-In | 3/24/2006 | 3/27/2006 | 3/27/2006 11:43:31 AM | A | PART |
|
|
PLEASE CALL DAVE OWEN AND HE WILL MEET THE INSPECTOR AT THE JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy u/g ok gate 85
|
ELE06-00362
| Final | 3/24/2006 | 3/27/2006 | 3/27/2006 10:16:05 AM | A | PASS |
|
|
mirela; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
|
ELE06-00986
| Permanent Service | 3/24/2006 | 3/27/2006 | 3/27/2006 9:44:44 AM | A | FAIL |
|
|
Leslie; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corr. met owner 300.10 &12 needs locknuts nipple meter and panel, 314.16 box fill, 110.3 rplace or jbox for damaged romex sheath334.30 staple romex 12" of panel, 330.40 approved fitting for MC, 250.90,92 bond nipple between meter panel,250.148 splice all equip together at jboxes,348.42 shall not conceal 90 degree flex fitting, install guy kit
|
ELE05-04252
| Conference | 3/27/2006 | 3/27/2006 | 3/27/2006 9:12:56 AM | A | DONE |
|
|
ok
|
ELE06-01015
| Electrical Rough-In | 3/24/2006 | 3/27/2006 | 3/27/2006 9:12:10 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/24/2006 at 4:31:29 PM. Contact: ###-####. r/i ok
|
ELE05-03604
| Final | 3/24/2006 | 3/27/2006 | 3/27/2006 8:05:31 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok no card
|