Inspections for the day of: Tuesday, March 27, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00221 INSP-Sprinkler Rough-in3/27/20073/27/20073/28/2007 12:03:20 PMPPART
OH rough-in is approved for cover.
BLD06-02535 FIRE-Final Inspection3/27/20073/27/20073/28/2007 8:11:29 AMPPASS
c/n items verified for completion, fire life safety finaled.
FIR07-00100 INSP-Sprinkler Rough-in/Hydro3/22/20073/27/20073/27/2007 3:54:53 PMPFAIL
OH hydrostatic test failed due to pressure loss at the guage and visible leakage at system piping, still need to provide resubmittals for changes in overhead piping.
FIR06-00595 INSP-Alarm Testing3/23/20073/27/20073/27/2007 3:52:58 PMPCANC
Pending correction of programing issues for descriptors and device address numbers matching an approved plan set.
FIR05-00574 INSP-Final Inspection3/26/20073/27/20073/27/2007 3:50:08 PMAPASS
Fire alarm permit finaled.
FIR05-00271 INSP-Final Inspection3/26/20073/27/20073/27/2007 3:49:07 PMAFAIL
Missing escutcheons at several locations, need to complete forward flow testing with a functional pitot guage.
FIR07-00194 INSP-Final Inspection3/26/20073/27/20073/27/2007 3:47:06 PMAPART
Need to replace one malfunctional a/v on the second floor west elevator lobby, also need to test elevator recall and associated devices when ready.
BLD06-03206 FIRE-Final Inspection3/26/20073/27/20073/27/2007 11:58:16 AMAFAIL
Need to provide emergency lighting as indicated on approved plans.
BLD07-00155 FIRE-Final Inspection3/26/20073/27/20073/27/2007 11:38:29 AMAPASS
Fire life safety is acceptable, one emergency light above the teller desk to be repaired today per contractor.
FIR06-00523 INSP-Alarm Testing3/26/20073/27/20073/27/2007 11:05:18 AMANR
Noted several items in need of correction including location and spacing of initiation and notification devices, cd ratings, manual pull station to be relocated, elevator monitoring, panel must be clear of all sprinkler supervisory signals prior to testing, missing signage at door to the FACP, etc.
FIR07-00238 INSP-Final Inspection3/26/20073/27/20073/27/2007 10:55:50 AMAPASS
The hood suppression system operated correctly under test conditions, inspection passed, permit finaled.