FIR07-00221
| INSP-Sprinkler Rough-in | 3/27/2007 | 3/27/2007 | 3/28/2007 12:03:20 PM | P | PART |
|
|
OH rough-in is approved for cover.
|
BLD06-02535
| FIRE-Final Inspection | 3/27/2007 | 3/27/2007 | 3/28/2007 8:11:29 AM | P | PASS |
|
|
c/n items verified for completion, fire life safety finaled.
|
FIR07-00100
| INSP-Sprinkler Rough-in/Hydro | 3/22/2007 | 3/27/2007 | 3/27/2007 3:54:53 PM | P | FAIL |
|
|
OH hydrostatic test failed due to pressure loss at the guage and visible leakage at system piping, still need to provide resubmittals for changes in overhead piping.
|
FIR06-00595
| INSP-Alarm Testing | 3/23/2007 | 3/27/2007 | 3/27/2007 3:52:58 PM | P | CANC |
|
|
Pending correction of programing issues for descriptors and device address numbers matching an approved plan set.
|
FIR05-00574
| INSP-Final Inspection | 3/26/2007 | 3/27/2007 | 3/27/2007 3:50:08 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR05-00271
| INSP-Final Inspection | 3/26/2007 | 3/27/2007 | 3/27/2007 3:49:07 PM | A | FAIL |
|
|
Missing escutcheons at several locations, need to complete forward flow testing with a functional pitot guage.
|
FIR07-00194
| INSP-Final Inspection | 3/26/2007 | 3/27/2007 | 3/27/2007 3:47:06 PM | A | PART |
|
|
Need to replace one malfunctional a/v on the second floor west elevator lobby, also need to test elevator recall and associated devices when ready.
|
BLD06-03206
| FIRE-Final Inspection | 3/26/2007 | 3/27/2007 | 3/27/2007 11:58:16 AM | A | FAIL |
|
|
Need to provide emergency lighting as indicated on approved plans.
|
BLD07-00155
| FIRE-Final Inspection | 3/26/2007 | 3/27/2007 | 3/27/2007 11:38:29 AM | A | PASS |
|
|
Fire life safety is acceptable, one emergency light above the teller desk to be repaired today per contractor.
|
FIR06-00523
| INSP-Alarm Testing | 3/26/2007 | 3/27/2007 | 3/27/2007 11:05:18 AM | A | NR |
|
|
Noted several items in need of correction including location and spacing of initiation and notification devices, cd ratings, manual pull station to be relocated, elevator monitoring, panel must be clear of all sprinkler supervisory signals prior to testing, missing signage at door to the FACP, etc.
|
FIR07-00238
| INSP-Final Inspection | 3/26/2007 | 3/27/2007 | 3/27/2007 10:55:50 AM | A | PASS |
|
|
The hood suppression system operated correctly under test conditions, inspection passed, permit finaled.
|