Inspections for the day of: Thursday, March 27, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00406 Electrical Rough-In3/27/20083/27/20083/27/2008 4:01:19 PMPPASS
joe Phone #: ###-#### ric ok
ELE06-02374 ELE-Aging Inspection3/27/20083/27/20083/27/2008 3:20:48 PM DONE
suc
ELE07-02302 Electrical Rough-In3/26/20083/27/20083/27/2008 2:33:04 PMPPART
Contact Steve Hess Phone #: ###-#### Internet Inspection Request from: Deb Gooden walls only anop
ELE07-03615 Final3/26/20083/27/20083/27/2008 1:36:09 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Alan Lusk met contractor, left correction notice, NEC 110.26 work space shall be maintained about electrical equipment- width, depth, dedicated space
ELE07-03772 Final3/26/20083/27/20083/27/2008 12:28:11 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok to final
ELE07-03771 Final3/26/20083/27/20083/27/2008 11:22:36 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Alan Lusk met contractor, left correction notice, NEC 110.26 shall maintain work space about equipment, 408.4 shall complete circuit directory, 210.52(E) shall provide receptacle at front of dwelling, 406.4 receptacles shall be securely fastened in place
ELE07-03613 Final3/26/20083/27/20083/27/2008 10:29:27 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Alan Lusk met contractor, left correction notice, NEC work space about equipment shall be maintained, 352.30(A) rnc shall be supported within 3' of panel, BCC all equipment sahll be installed
ELE07-03963 Final3/26/20083/27/20083/27/2008 9:36:47 AMAPASS
Reinspection. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST corrections made, ok to final
ELE08-00669 Permanent Service3/26/20083/27/20083/27/2008 8:47:12 AMAPASS
zane Phone #: ###-#### p/s u/g n ok
ELE08-00688 Electrical Rough-In3/26/20083/27/20083/27/2008 7:55:49 AMAPASS
Reinspect Phone #: ###-#### Internet Inspection Request from: BRENDA HURST corrections made, ric ok walls and ceiling, called contractor