Inspections for the day of: Thursday, March 27, 2008.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00474 FIR-Aging Inspection3/27/20083/27/20083/28/2008 3:46:29 PMPDONE
Peak alarm to schedule testing for final acceptance of permit work.
FIR08-00165 INSP-Sprinkler Rough-in3/27/20083/27/20083/28/2008 3:45:24 PMPPART
System modifications are acceptable at areas as circled and initialed on plan set, three training rooms to the west side are not yet complete.
BLD06-00693 FIRE-Final Inspection3/27/20083/27/20083/28/2008 3:42:52 PMPPASS
Items on correction notice are complete, structrual inspector to verifiy adjusted door closures at apartment units are acceptable, fire life safety finaled.
BLD05-00926 FIRE-Final Inspection3/27/20083/27/20083/28/2008 3:40:56 PMPPASS
Fire life safety finaled.
FIR08-00113 INSP-Final Inspection3/27/20083/27/20083/27/2008 5:23:51 PMPFAIL
Need to relocate the pendent head at the north utility room due to cabinet obstruction.
FIR08-00089 INSP-Final Inspection3/26/20083/27/20083/27/2008 5:21:50 PMPFAIL
Need to relocate or remove the smoke detector at the new nac panel, noted some overspaced notification devices, tenant floorplan has been modified to include an adjacent space-building permit is under review for approval. No alarm testing completed today.
FIR08-00088 INSP-Final Inspection3/26/20083/27/20083/27/2008 5:16:13 PMPFAIL
Drawings do not match floorplan, one workroom not shown on plans will need notification, noted overspaced strobes at three locations, one av has been deleted due to room changes, no devices tested at this time.
FIR06-00540 INSP-Final Inspection3/25/20083/27/20083/27/2008 4:22:54 PMPNR
FIR06-00595 INSP-Final Inspection3/27/20083/27/20083/27/2008 4:22:01 PMPNR
Inspection to be rescheduled.
BLD07-03251 FIRE-Final Inspection3/26/20083/27/20083/27/2008 4:21:15 PMPPART
Fire life safety field inspection completed satisfactory, final pending project related fire alarm final for verification of corrected defficiencies and FA interconnection to mag locks for access controled egress at three locations, also missing permanent max. occupant load signs at one assembly room.
FIR08-00051 INSP-Final Inspection3/26/20083/27/20083/27/2008 4:16:55 PMPPASS
Fire sprinkler permit final inspection passed.
FIR08-00095 INSP-Final Inspection3/26/20083/27/20083/27/2008 2:21:15 PMPPASS
Tenant remodel fire alarm testing passed inspection, permit finaled.
FIR08-00039 INSP-Sprinkler Rough-in3/26/20083/27/20083/27/2008 1:54:50 PMAFAIL
One upright head at the womens restroom is blocked by adjacent ductwork, one ssu at the mens restroom is obstructed by the top joist cord which extends below and directly next to the deflector, missing EQ brace at the last piece of main. Areas approved for cover include the hall 116, sacristy 115, and the narthex entry 101-see stamped plans for initialed locations. Also verified resubmittals match installation at areas where field modifications were done.
BLD08-00056 FIRE-Final Inspection3/26/20083/27/20083/27/2008 12:52:25 PMAPASS
Fire life safety inspection passed. Fire alarm work tested per separate permit and completed final by K. Roule.
FIR07-01012 FIR-Aging Inspection3/27/20083/27/20083/27/2008 12:47:54 PM DONE
Work in progress, pending site inspection request.
FIR07-00835 INSP-Supply line flush3/26/20083/27/20083/27/2008 12:47:00 PMPPART
UG fire supply line flush completed satisfactory post hydrostatic test.
FIR08-00207 INSP-Sprinkler Rough-in3/26/20083/27/20083/27/2008 12:45:33 PMAPART
OH fire sprinkler system modifications are approved for cover at the drop ceilings, minor floorplan changes and sprinkler head location adjustments accepted, final pending ceiling tile and escutcheons.
FIR07-00835 INSP-Sprinkler Rough-in/Hydro3/26/20083/27/20083/27/2008 12:43:24 PMAPART
UG fire supply line hydrostatic test passed inspection.
FIR08-00117 INSP-Final Inspection3/26/20083/27/20083/27/2008 12:42:30 PMAPART
Scope of work is not complete due to pending demolition of the photo room, conference room pendent heads are satisfactory. Also noted non-functional outside waterflow bell to be repaired and verified at next site visit for permit final.
FIR07-00958 INSP-Sprinkler Rough-in3/26/20083/27/20083/27/2008 12:34:50 PMAFAIL
Red-lined areas on stamped plan set in need of revision prior to approval for cover including blocked or overspaced upright heads at various locations and missing coverage at a storage room. Not all areas ready for inspection at this time, see plans for annotations.
FIR08-00205 INSP-Final Inspection3/26/20083/27/20083/27/2008 8:12:49 AMPCANC
mike Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
FIR08-00207 INSP-Supply line flush3/26/20083/27/20083/27/2008 12:00:00 AMACANC
ben Phone #: ###-####