FIR11-00496
| INSP-Sprinkler Rough-in | 3/26/2012 | 3/27/2012 | 3/30/2012 11:01:33 AM | P | PART |
|
|
Reference approved plan set for locations marked and dated as okayed for cover at the 3rd floor south end.
|
FIR12-00139
| INSP-Sprinkler Rough-in | 3/27/2012 | 3/27/2012 | 3/27/2012 2:51:49 PM | P | PART |
|
|
Overhead work at the grid ceilings approved for cover.
|
FIR09-00645
| INSP-Final Inspection | 3/20/2012 | 3/27/2012 | 3/27/2012 2:50:56 PM | A | FAIL |
|
|
Noted one non-functional tamper switch at the 1st floor control valve. Activation of the manual pull station initiated elevator recall. Transformer back box needs secured.
|
FIR09-00643
| INSP-Final Inspection | 3/20/2012 | 3/27/2012 | 3/27/2012 2:47:35 PM | A | PASS |
|
|
Scope of fire alarm permit work passed inspection. Note- fire tap has not been installed per original plan. Resubmittal not required in this case.
|
BLD12-00133
| FIRE-Final Inspection | 3/27/2012 | 3/27/2012 | 3/27/2012 2:42:58 PM | P | PASS |
|
|
Fire life safety inspection passed.
|