Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02402 Final3/27/20133/27/20133/27/2013 2:19:10 PMPNH
Please call Bill if you have any questions. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast no access due to painting exterior of house
ELE12-03031 Final3/27/20133/27/20133/27/2013 1:48:37 PMPNH
Phone #: ###-#### >> Inspection requested via web by Mark M unable to make contact to perform inspection
ELE12-02130 Final3/27/20133/27/20133/27/2013 1:25:17 PMPPASS
Pease call Bill if you have any questions. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast trench final ok
ELE12-02751 Final3/27/20133/27/20133/27/2013 1:22:03 PMPFAIL
Please call Bill if you have any questions Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast
210.8 (A)(6)- Appliance garage- Where recepticals are installed to serve counter top surfaces they shall have GFCI protection.
110.7- Complete wiring installation- bed arcfault breaker will not hold.
110.22 Each disconnecting means shall be marked to indicate its purpose.
Due to HVAC code residential garages from floor to 18" above floor shall be considered class 1 division 1 due to fuel storage and lack of air movement. Recepticals shall be installed above 18" from floor
GCE13-00045 GCE-Courtesy3/27/20133/27/20133/27/2013 12:11:44 PMPDONE
amy - ###-#### Discussed overhead roof clearences, interior electrical room egress illumination and panic hardware.
ESC12-01129 General Inspection3/27/20133/27/20133/27/2013 10:24:51 AM PASS
ELE13-00695 Conference3/26/20133/27/20133/27/2013 10:02:50 AMADONE
john - call 15 mins prior for access Phone #: ###-#### Discussed master bed and bath remodel code required outlets for bed and bath, smoke detectors, NM cable supports on stud members
ELE13-00337 Final3/26/20133/27/20133/27/2013 9:17:45 AMAFAIL
kenny or todd Phone #: ###-####
As per installation instructions additional GFCI protection required for floor heat.
Conduit on back deck to disconnect shall be strapped.
ELE13-00676 Final3/26/20133/27/20133/27/2013 8:46:32 AMAPASS
Phone #: ###-#### >> Inspection requested via web by sam petterson Final ok
ELE13-00688 Final3/26/20133/27/20133/27/2013 8:38:53 AMAPASS
Phone #: ###-#### >> Inspection requested via web by sam petterson Final ok
ELE11-02806 Rough-In Permanent Service3/26/20133/27/20133/26/2013 2:59:19 PMAPASS
3rd floor rough in walls call mike 1/2 prior Phone #: ###-#### >> Inspection requested via web by Shawna Gates New tenant space wall rough in ok cover
ELE11-02806 Electrical Rough-In3/26/20133/27/20133/26/2013 11:55:28 AMPCANC
3rd floor atrium wall rough in...call mike 1/2 prior Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates