Inspections for the day of: Thursday, March 27, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00693 Final3/26/20143/27/20143/27/2014 3:51:58 PMPPASS
Conduit work >> Inspection requested via web by ERIC CENTERS Final ok
ELE14-00697 Electrical Rough-In3/27/20143/27/20143/27/2014 3:26:52 PMPFAIL
MIke Phone #: ###-#### Back patio and bird room. Went back to find tool left on job. Found splice buried in wall.
BCC 4-05-17- It shall be unlawful to hide a splice in violation with the National Electric Code behind insulation to conceal it from view.
NEC 300.15- Boxes where required- Nonmetallic sheathed cable, a box shall be installed at each conductor splice.
ELE14-00142 Electrical Rough-In3/27/20143/27/20143/27/2014 2:36:36 PMPPASS
Please inspect open trenches and well pump... >> Inspection requested via web by Kevin Perez Under ground landscape, future pool, and back garage conduits rough in ok cover
ELE14-00056 Final3/27/20143/27/20143/27/2014 1:51:38 PMPPASS
Please call and I will meet you there. Thank you
Eric Phone #: ###-#### >> Inspection requested via web by Eric Brown Final ok
ELE13-00892 Final3/27/20143/27/20143/27/2014 1:17:53 PMPPASS
early as poss // call Wally (father) to meet Phone #: ###-#### Final ok
ELE12-01829 Final3/27/20143/27/20143/27/2014 12:09:07 PMPPASS
Met contractor on job near and walked over and inspected. Final ok
ELE14-00485 Final3/26/20143/27/20143/27/2014 10:28:02 AMAPASS
reinspect Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Final ok
ELE14-00410 Final3/27/20143/27/20143/27/2014 10:08:41 AMAPASS
please call half hour prior to inspection time. thank you, larry Phone #: ###-#### >> Inspection requested via web by larry samples UL listing confirmed Final ok
ELE14-00693 Electrical Rough-In3/26/20143/27/20143/27/2014 9:52:56 AMAPASS
Conduit work Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS Baseball locker room rough in ok
ELE14-00185 Electrical Rough-In3/26/20143/27/20143/27/2014 9:12:57 AMAPASS
Need the the West end up and down for cover thanks Phone #: ###-#### >> Inspection requested via web by Brad Baker Wall and hard lids rough in ok cover
GCE13-00149 GCE-Final3/25/20143/27/20143/27/2014 8:46:52 AMAPASS
(Mandatory Inspection) Mike ###-#### call for gate code B&B Electric ###-#### Final ok