Inspections for the day of: Friday, March 27, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02886 ELE-Aging Inspection3/27/20153/27/20153/27/2015 1:59:40 PM DONE
still under construction
ELE15-00223 Final3/27/20153/27/20153/27/2015 1:58:16 PMPNR
Key in front outlet Phone #: ###-#### Inspection requested via web by TOM BICANDI sign on door for wet floors, called contractor to recall
ELE14-02373 Electrical Rough-In3/26/20153/27/20153/27/2015 1:55:58 PMPPASS
Site under ground inspection for 4 each pole bases and conduit in front of HL and retaining wall south east corner of G. Building permit number BLD13-02064. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
ELE14-02067 Electrical Rough-In3/26/20153/27/20153/27/2015 1:21:30 PMPPASS
Rough-in inspection SNF L Electrical room L125 walls only for sheet rock and gear install. Building permit number BLD13-00191. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover as requested
ELE15-00816 Temporary Service3/27/20153/27/20153/27/2015 11:34:04 AMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Burke t/s u/g n ok
ELE14-03163 Final3/27/20153/27/20153/27/2015 11:15:59 AMPFAIL
Keith-if locked call Keith for access Phone #: ###-#### called, left correction notice, BCC shall change room count from 1 to 10 rooms on permit, NEC 110.26(E) there shall be no foreign systems in dedicated panel space i.e. ducts or piping, 334.30 shall securely support nm cable within 12" of panel, 300.4 shall provide cable protection if over 1/14" to edge of hole or cable
ELE14-03399 Final3/26/20153/27/20153/27/2015 10:40:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Jay Symonds ok final
ELE15-00773 Temporary Service3/26/20153/27/20153/27/2015 9:56:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE15-00771 Temporary Service3/26/20153/27/20153/27/2015 9:34:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE15-00775 Rough-In Permanent Service3/24/20153/27/20153/27/2015 8:58:41 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
ELE14-03219 Electrical Rough-In3/26/20153/27/20153/27/2015 7:56:08 AMAPASS
Ceiling inspect for the Telecom room. Contact is Justin Bieker. Phone #: ###-#### Inspection requested via web by Richard Montgomery ok cover ceiling as requested