FIR14-00750
| INSP-Sprinkler Rough-in | 3/27/2015 | 3/27/2015 | 3/31/2015 11:53:48 AM | P | PART |
|
|
Inspection to verify completion of previously noted correction items at the dry system. Finished 3/27.
|
FIR15-00096
| INSP-Sprinkler Rough-in | 3/26/2015 | 3/27/2015 | 3/31/2015 11:43:59 AM | P | PART |
|
|
Ref. to inspection notes dated 3/30
|
FIR14-00866
| INSP-Sprinkler Rough-in | 3/26/2015 | 3/27/2015 | 3/31/2015 11:42:15 AM | P | PART |
|
|
Completed rough-in inspection for the remainder of the 4th floor living units only as noted on stamped plans. Items noted include; overspaced coverage at unit 405, missing coverage at units 430 and 432. Need to install flushing caps per plan notes.
|
BLD14-03666
| FIRE-Final Inspection | 3/25/2015 | 3/27/2015 | 3/27/2015 2:07:37 PM | A | PART |
|
|
Final pending door hardware and posting of one fire extinguisher per plan. Remainder okayed.
|
BLD14-03595
| FIRE-Final Inspection | 3/27/2015 | 3/27/2015 | 3/27/2015 1:24:46 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR14-00889
| INSP-Final Inspection | 3/26/2015 | 3/27/2015 | 3/27/2015 1:04:48 PM | A | PASS |
|
|
Completed dry system trip test, riser supervision, final walkthrough and verification of noted correction items.
|
FIR14-00243
| INSP-Final Inspection | 3/26/2015 | 3/27/2015 | 3/27/2015 1:00:27 PM | A | PASS |
|
|
Remainder of fire alarm work passed final inspection and testing.
|
FIR14-00316
| INSP-Final Inspection | 3/26/2015 | 3/27/2015 | 3/27/2015 10:44:01 AM | A | NH |
|
|
No access
|
FIR14-00437
| INSP-Final Inspection | 3/26/2015 | 3/27/2015 | 3/27/2015 10:42:06 AM | A | NH |
|
|
No access to complete inspection
|
BLD14-03715
| FIRE-Final Inspection | 3/25/2015 | 3/27/2015 | 3/27/2015 10:40:20 AM | A | PASS |
|
|
Fire life safety inspection completed. However cannot be finaled until project related fire alarm work is inspected and approved. Also noted missing smoke seal at the main entry corridor door frame.
|
FIR15-00109
| INSP-Final Inspection | 3/25/2015 | 3/27/2015 | 3/27/2015 10:35:54 AM | A | PASS |
|
|
Fire sprinkler permit work passed final walkthrough.
|
FIR15-00186
| INSP-Final Inspection | 3/26/2015 | 3/27/2015 | 3/27/2015 7:15:12 AM | A | PASS |
|
|
Fire sprinkler permit work finaled.
|
FIR15-00186
| INSP-Sprinkler Rough-in | 3/26/2015 | 3/27/2015 | 3/26/2015 5:54:45 PM | A | PART |
|
|
Fire sprinkler modifications okay for cover.
|