ELE17-00599
| Electrical Rough-In | 3/27/2017 | 3/27/2017 | 3/27/2017 2:27:48 PM | P | FAIL |
|
|
Cover inspection before sheetrock Phone #: ###-#### Inspection requested via web by Steve Craig 310.15 B3 Adjustment factors required for more than 9 current carrying conductors. Too many cables in stud knock outs. Loose MC connector on neighboring unit recep. West wall.
|
ELE16-04017
| Electrical Rough-In | 3/27/2017 | 3/27/2017 | 3/27/2017 1:47:41 PM | P | PASS |
|
|
L1 deck pour 3 Phone #: ###-#### Inspection requested via web by Debby Pierce ok to cover
|
ELE17-00808
| Electrical Rough-In | 3/27/2017 | 3/27/2017 | 3/27/2017 1:13:40 PM | P | PASS |
|
|
Call Mike Donelson with questions ###-####. Phone #: ###-#### Inspection requested via web by Samatha Solberg Master bed, bath, closet and hall bath only rough in ok
|
ELE17-00485
| Electrical Rough-In | 3/27/2017 | 3/27/2017 | 3/27/2017 12:53:06 PM | P | PASS |
|
|
Johnny Phone #: ###-#### Kitchen, Laundry only rough in ok
|
ELE17-00799
| Electrical Rough-In | 3/26/2017 | 3/27/2017 | 3/27/2017 10:54:08 AM | A | PASS |
|
|
rough in on led pole retrofit Phone #: ###-#### Inspection requested via web by Tim Dunlop Checked LED lamps for listing. Bypassing Ballest
|
ELE17-00720
| Electrical Rough-In | 3/24/2017 | 3/27/2017 | 3/27/2017 9:45:52 AM | A | PASS |
|
|
ceiling grid; Robert Phone #: ###-#### Ceiling only ok to cover
|
ELE17-00472
| Electrical Rough-In | 3/23/2017 | 3/27/2017 | 3/27/2017 8:46:12 AM | A | PASS |
|
|
underground; Erik Phone #: ###-#### Underground from garage to house only OK to cover
|