BLD16-00172
| FIRE-Final Inspection | 3/27/2017 | 3/27/2017 | 3/27/2017 2:28:34 PM | A | CANC |
|
|
|
BLD16-00172
| FIRE-Final Inspection | 3/27/2017 | 3/27/2017 | 3/27/2017 2:28:14 PM | P | CANC |
|
|
Inspection scheduled for 28MAR2017, this request is cancelled.
|
FIR16-00606
| INSP-Sprinkler Rough-in/Hydro | 3/27/2017 | 3/27/2017 | 3/27/2017 2:19:44 PM | P | FAIL |
|
|
Rough in inspection for level 2 corridor main complete. Rough to cover inspection performed on level 4, pipe scheduling did not match the city approved drawings, stopped inspection after finding 5 locations with too many heads off of 1 inch pipe. Pipe scheduling will need to be changed to coincide with city approve drawings, piping cannot be covered until repairs are made and a re-inspection is performed
|
FIR16-00319
| INSP-Sprinkler Rough-in | 3/27/2017 | 3/27/2017 | 3/27/2017 12:52:51 PM | P | PASS |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping, all area's approved for cover.
|
FIR17-00096
| INSP-Sprinkler Rough-in | 3/24/2017 | 3/27/2017 | 3/27/2017 10:37:07 AM | A | PART |
|
|
Rough to cover inspection for fire sprinkler piping/pendant heads above hardlids complete, notated the city approved drawings with red ink area's approved for cover.
|
BLD16-04192
| FIRE-Final Inspection | 3/23/2017 | 3/27/2017 | 3/27/2017 9:06:18 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/compete.
|
BLD16-02645
| FIRE-Final Inspection | 3/24/2017 | 3/27/2017 | 3/27/2017 8:53:00 AM | A | PASS |
|
|
Final fire sprinkler inspection complete, final fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is in place. Final life fire safety inspection passed/complete.
|
FIR16-00722
| INSP-Final Inspection | 3/24/2017 | 3/27/2017 | 3/27/2017 8:51:51 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR17-00129
| INSP-Final Inspection | 3/24/2017 | 3/27/2017 | 3/27/2017 8:51:12 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|