Inspections for the day of: Monday, March 27, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-00172 FIRE-Final Inspection3/27/20173/27/20173/27/2017 2:28:34 PMACANC
BLD16-00172 FIRE-Final Inspection3/27/20173/27/20173/27/2017 2:28:14 PMPCANC
Inspection scheduled for 28MAR2017, this request is cancelled.
FIR16-00606 INSP-Sprinkler Rough-in/Hydro3/27/20173/27/20173/27/2017 2:19:44 PMPFAIL
Rough in inspection for level 2 corridor main complete. Rough to cover inspection performed on level 4, pipe scheduling did not match the city approved drawings, stopped inspection after finding 5 locations with too many heads off of 1 inch pipe. Pipe scheduling will need to be changed to coincide with city approve drawings, piping cannot be covered until repairs are made and a re-inspection is performed
FIR16-00319 INSP-Sprinkler Rough-in3/27/20173/27/20173/27/2017 12:52:51 PMPPASS
Rough to cover inspection complete for overhead fire sprinkler piping, all area's approved for cover.
FIR17-00096 INSP-Sprinkler Rough-in3/24/20173/27/20173/27/2017 10:37:07 AMAPART
Rough to cover inspection for fire sprinkler piping/pendant heads above hardlids complete, notated the city approved drawings with red ink area's approved for cover.
BLD16-04192 FIRE-Final Inspection3/23/20173/27/20173/27/2017 9:06:18 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/compete.
BLD16-02645 FIRE-Final Inspection3/24/20173/27/20173/27/2017 8:53:00 AMAPASS
Final fire sprinkler inspection complete, final fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is in place. Final life fire safety inspection passed/complete.
FIR16-00722 INSP-Final Inspection3/24/20173/27/20173/27/2017 8:51:51 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00129 INSP-Final Inspection3/24/20173/27/20173/27/2017 8:51:12 AMAPASS
Final fire alarm inspection passed/complete