ELE18-00940
| Final | 3/26/2018 | 3/27/2018 | 3/27/2018 2:06:43 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Ok final.
|
ELE17-04192
| Final | 3/27/2018 | 3/27/2018 | 3/27/2018 12:22:18 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson 1. Lockout for hood. 2. A/C max fuse is 35. 40a brkr installed, and 60a fuses at A/C. 3. GFI b;y back french doors not tamper resist. 4. Disconnect needed for furnace. Not within sight. 5. P-8 style filler plate needed for WP on garage.
|
ELE18-01058
| Electrical Rough-In | 3/26/2018 | 3/27/2018 | 3/27/2018 10:03:59 AM | A | PASS |
|
|
Mike Phone #: ###-#### Ok cover admissions booth and snack bar.
|
ELE17-03967
| Final | 3/26/2018 | 3/27/2018 | 3/27/2018 9:26:59 AM | A | PASS |
|
|
###-#### Ok final.
|
ELE18-01089
| Electrical Rough-In | 3/26/2018 | 3/27/2018 | 3/27/2018 8:54:10 AM | A | PASS |
|
|
Bedroom addition Phone #: ###-#### Inspection requested via web by Shaun Kirkman Ok cover bed.
|
ELE14-00144
| ELE-Aging Inspection | 3/27/2018 | 3/27/2018 | 3/27/2018 7:31:37 AM | | DONE |
|
|
Please schedule for a final inspection.
|