Inspections for the day of: Friday, March 27, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03829 Electrical Rough-In3/26/20203/27/20203/27/2020 2:11:09 PMPPASS
Rough-In inspection 1st floor walls on the west end.
Contact Shawn Evins.
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed 1 siding and cover pior to inspection, any cover in anyway prior to an electrical inspection will be required to be removed completely until the same has been inspected as per Boise city ordinance 4-05-23. Will verify a city appoved set of prints on site next inspection.
As noted on contractor print. Level 1 top-out 4' only and electrical rooms only rough in ok cover.
ELE20-01076 Electrical Rough-In3/27/20203/27/20203/27/2020 1:27:03 PMPPASS
Please call ahead 30 mins for accesss Phone #: ###-#### Inspection requested via web by John VanZandt
Upstairs jack and jill bathrooms changing to 2 full bathrooms. Rough in ok cover.
ELE20-01065 Final3/26/20203/27/20203/27/2020 10:55:56 AMAPASS
Please call Lance for the exact location of the outlets. Thank you. Phone #: ###-#### Inspection requested via web by Kyle Lott
Final ok
ELE20-01065 Electrical Rough-In3/27/20203/27/20203/27/2020 10:55:07 AMPPASS
Please call Lance for the exact location of the outlets. Thank you. Phone #: ###-#### Inspection requested via web by Kyle Lott
2 new receptacles fished in to existing walls of an office. Rough in ok cover.
ELE19-00601 Electrical Rough-In3/26/20203/27/20203/27/2020 10:32:25 AMAPASS
Cover.... Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Level 1 kitchen walls rough in ok cover.
ELE20-01099 Electrical Rough-In3/26/20203/27/20203/27/2020 9:57:36 AMAPASS
to cover // Larry Phone #: ###-####
1 area in office in basement will need a receptacle outlet installed in existing outside wall with in 6' of storage area as per 210.52(A).
Basement remodel rough in ok cover.
ELE20-00216 Final3/26/20203/27/20203/27/2020 9:25:16 AMAFAIL
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Garage lights not working.
AC max overcurrent 30 amp, 40 amp installed.
ELE20-00949 Rough-In Permanent Service3/26/20203/27/20203/27/2020 8:56:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard
Rough in ok cover