Inspections for the day of: Monday, March 28, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00057 INSP-Final Inspection3/25/20053/28/20053/28/2005 12:00:00 AMACANC
Contact: Vance; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
BLD05-00298 FIRE-Final Inspection3/25/20053/28/20053/28/2005 12:00:00 AMAPASS
Fire life safety finaled 3/28/2005 11:56:06 AM
FIR04-00684 INSP-Sprinkler Rough-in/Hydro3/26/20053/28/20053/28/2005 12:00:00 AMAPART
Hydro test for the standpipe and the third floor failed. Rough-in for the fourth floor sidewalls in rooms passed. 3/28/2005 12:03:46 PM
BLD04-02195 FIRE-Final Inspection3/27/20053/28/20053/28/2005 12:00:00 AMPFAIL
No permit had been issued for the hood suppression system but work has been complete. Pull station is too close to hood, no fire extinguishers installed. Hood is not connected to the existing fire alarm system. We went over live safety review note requirements with the general contractor. I request that Pete with Coliers contact me about the fire alarm requirements. 3/28/2005 4:04:36 PM
BLD05-00133 FIRE-Final Inspection3/28/20053/28/20053/28/2005 12:00:00 AMPPASS
fire life safety finaled 3/28/2005 1:18:55 PM
FIR05-00168 INSP-Final Inspection3/28/20053/28/20053/28/2005 12:00:00 AMPPASS
fire sprinkler finaled 3/28/2005 2:29:42 PM
BLD04-02887 FIRE-Final Inspection3/28/20053/28/20053/28/2005 12:00:00 AMPFAIL
Repair three exit signs and one emergency light. Repair remote annunciators and provide one additional duct smoke to the hvac unit number three. 3/28/2005 3:59:05 PM
FIR05-00126 INSP-Sprinkler Rough-in/Hydro3/28/20053/28/20053/28/2005 12:00:00 AMPFAIL
Could not do inspection since resubmittals are required for plans 3/28/2005 4:01:58 PM
FIR05-00145 INSP-Final Inspection3/28/20053/28/20053/28/2005 12:00:00 AMPPASS
spindell; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD05-00082 FIRE-Final Inspection3/28/20053/28/20053/28/2005 12:00:00 AMPPASS
fire life saftey finaled
FIR04-00552 INSP-Final Inspection3/24/20053/28/20053/28/2005 12:00:00 AMPFAIL
Water meter is the wrong size, two pendants in the basement are too close to soffits. Still need to do all of the final signoff items. 3/28/2005 12:11:28 PM
MIS04-00262 FIR-Final3/25/20053/28/20053/28/2005 12:00:00 AMPCANC
Please call prior to inspection so she can meet ya there///reham ###-#### Still need the plans resubmitted. I told her to call Carl Westfall since she misunderstood what was required for city approval. 3/28/2005 2:50:43 PM