ELE05-04620
| ELE-Aging Inspection | 3/28/2006 | 3/28/2006 | 4/3/2006 2:33:37 PM | | FAIL |
|
|
corr called 210.52(A&C) outlet spacing walls and countertops, 314.43 no screws in plastic boxes 300.4 nail plates and 11/4", 314.20 outside boxes shall be flush with siding,
|
ELE06-00711
| Conference | 3/28/2006 | 3/28/2006 | 3/28/2006 4:29:24 PM | P | DONE |
|
|
conference on use of fixture whip not allowed for branch circuit wiring to reccess fixtures, 410.67 (A B C)
|
ELE05-04071
| Electrical Rough-In | 3/27/2006 | 3/28/2006 | 3/28/2006 3:48:41 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 3/27/2006 at 1:17:27 PM. Contact: ###-####. r/i walls anop
|
ELE05-02847
| Final | 3/27/2006 | 3/28/2006 | 3/28/2006 2:23:15 PM | P | FAIL |
|
|
butch; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr. called 250.148 &122 shall splice all equip grd together at relay jbox and grd box with #10 110.26(F)(1) remove water pipe from in front of panel phone rm
|
ELE06-01053
| Electrical Rough-In | 3/28/2006 | 3/28/2006 | 3/28/2006 1:31:34 PM | P | FAIL |
|
|
Justin; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corr. called 300.4(A)(1)&(D), nail plates and 11/4" for MC and ENT, 330.30(B) 358.30 (A&B) shall strap MC 12" of boxes, EMT 3ft of boxes, 410.67(A B C) shall not use fixture whips for reccess fixtures shall be branch circuit wiring to jbox on fixture
|
ELE06-01034
| Permanent Service | 3/27/2006 | 3/28/2006 | 3/28/2006 12:01:45 PM | P | CANC |
|
|
Kevin -- prefer after 1PM; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong contractor called and canceled he will reschedule
|
ELE06-00856
| Conference | 3/28/2006 | 3/28/2006 | 3/28/2006 11:42:59 AM | A | DONE |
|
|
ok answered questions contractor had on cover requirements for u/g wiring in airport fenced in area
|
ELE06-01039
| Temporary Service | 3/27/2006 | 3/28/2006 | 3/28/2006 9:56:29 AM | A | PASS |
|
|
charlie Internet Inspection Request from: Melyne Davis t/s o/h new ok
|
ELE06-01023
| Temporary Service | 3/27/2006 | 3/28/2006 | 3/28/2006 9:37:08 AM | A | PASS |
|
|
charlie Internet Inspection Request from: Melyne Davis t/s u/g new ok
|
ELE06-01047
| Electrical Rough-In | 3/27/2006 | 3/28/2006 | 3/28/2006 9:04:28 AM | A | PART |
|
|
Lynn -- rough in ufer ground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong electrode ok
|
ELE06-00984
| Permanent Service | 3/28/2006 | 3/28/2006 | 3/28/2006 8:34:41 AM | A | PASS |
|
|
Ryan ###-#### -- okay for 3-28 AM per Jack Frank; call 1st for access 3-28-06 eus p/s o/h new ok
|
ELE06-00984
| Final | 3/27/2006 | 3/28/2006 | 3/28/2006 12:00:00 AM | A | CANC |
|
|
Ryan -- call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong /// Cancel per Ryan as suggested by Jack Frank 3-28-06 eus
|