Inspections for the day of: Tuesday, March 28, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04620 ELE-Aging Inspection3/28/20063/28/20064/3/2006 2:33:37 PM FAIL
corr called 210.52(A&C) outlet spacing walls and countertops, 314.43 no screws in plastic boxes 300.4 nail plates and 11/4", 314.20 outside boxes shall be flush with siding,
ELE06-00711 Conference3/28/20063/28/20063/28/2006 4:29:24 PMPDONE
conference on use of fixture whip not allowed for branch circuit wiring to reccess fixtures, 410.67 (A B C)
ELE05-04071 Electrical Rough-In3/27/20063/28/20063/28/2006 3:48:41 PMPPART
Scheduled by a contractor via Hello! on 3/27/2006 at 1:17:27 PM. Contact: ###-####. r/i walls anop
ELE05-02847 Final3/27/20063/28/20063/28/2006 2:23:15 PMPFAIL
butch; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
corr. called 250.148 &122 shall splice all equip grd together at relay jbox and grd box with #10 110.26(F)(1) remove water pipe from in front of panel phone rm
ELE06-01053 Electrical Rough-In3/28/20063/28/20063/28/2006 1:31:34 PMPFAIL
Justin; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
corr. called 300.4(A)(1)&(D), nail plates and 11/4" for MC and ENT, 330.30(B) 358.30 (A&B) shall strap MC 12" of boxes, EMT 3ft of boxes, 410.67(A B C) shall not use fixture whips for reccess fixtures shall be branch circuit wiring to jbox on fixture
ELE06-01034 Permanent Service3/27/20063/28/20063/28/2006 12:01:45 PMPCANC
Kevin -- prefer after 1PM; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong contractor called and canceled he will reschedule
ELE06-00856 Conference3/28/20063/28/20063/28/2006 11:42:59 AMADONE
ok answered questions contractor had on cover requirements for u/g wiring in airport fenced in area
ELE06-01039 Temporary Service3/27/20063/28/20063/28/2006 9:56:29 AMAPASS
charlie Internet Inspection Request from: Melyne Davis t/s o/h new ok
ELE06-01023 Temporary Service3/27/20063/28/20063/28/2006 9:37:08 AMAPASS
charlie Internet Inspection Request from: Melyne Davis t/s u/g new ok
ELE06-01047 Electrical Rough-In3/27/20063/28/20063/28/2006 9:04:28 AMAPART
Lynn -- rough in ufer ground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong electrode ok
ELE06-00984 Permanent Service3/28/20063/28/20063/28/2006 8:34:41 AMAPASS
Ryan ###-#### -- okay for 3-28 AM per Jack Frank; call 1st for access 3-28-06 eus
p/s o/h new ok
ELE06-00984 Final3/27/20063/28/20063/28/2006 12:00:00 AMACANC
Ryan -- call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong /// Cancel per Ryan as suggested by Jack Frank 3-28-06 eus