ELE06-01048
| Electrical Rough-In | 3/28/2006 | 3/28/2006 | 3/28/2006 4:43:47 PM | P | PASS |
|
|
Mike -- underground reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corr made,ok to cover u/g only
|
ELE06-00292
| Electrical Rough-In | 3/28/2006 | 3/28/2006 | 3/28/2006 3:59:36 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/28/2006 at 11:07:54 AM. Contact: ###-####. met owner, left corr notice,300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member 210.52(A)(1) receptacles shall be installed so that no point measured horizontally along the floor line is more than 6' from an outlet, BCC all make-up shall be done
|
ELE05-04290
| Final | 3/28/2006 | 3/28/2006 | 3/28/2006 2:58:07 PM | P | FAIL |
|
|
Robert -- location back of office; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, set up meeting when he calls back in, 314.23(C) enclosure mounted in finished surface shall be rigidly secured, BCC ceiling cover not approved
|
ELE04-01948
| Final | 3/28/2006 | 3/28/2006 | 3/28/2006 2:07:18 PM | P | FAIL |
|
|
please call 15 min prior to meet for access//dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met contractor, he asked for electronic corr notice rather than paper,110.26(F)(1)(a) there shall be no foreign piping systems in dedicated electrical space,width and depth of equipment from floor to structural ceiling, 314.25 each box shall have a cover
|
ELE06-01049
| Electrical Rough-In | 3/28/2006 | 3/28/2006 | 3/28/2006 1:06:25 PM | P | FAIL |
|
|
any questions please call Mike Dale; Phone #: ###-#### Internet Inspection Request from: Jeff Radford called, left message, left corr notice, 334.30 nm cable shall be stapled within 12" of boxes, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.70(2)(b) lighting outlet shall be switched and installed on exterior side of outdoor entrances or exits with grade level access, BCC no violations shall be retained, could not check attic, verify heater listing and load (wiring quite hot)
|
ELE06-00248
| Electrical Rough-In | 3/28/2006 | 3/28/2006 | 3/28/2006 11:41:40 AM | A | NH |
|
|
UNDERGROUND CONDUIT; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contr, left message, couldn't get in gate, said to recall
|
ELE06-01048
| Electrical Rough-In | 3/27/2006 | 3/28/2006 | 3/28/2006 10:10:35 AM | A | FAIL |
|
|
Mike -- trench with a conduit; reconnecting svc to new mobile home; Western Village Mobile Park; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, told him conduit was not deep enough, did not leave corr notice, he will recall
|
ELE06-00938
| Electrical Rough-In | 3/27/2006 | 3/28/2006 | 3/28/2006 9:42:49 AM | A | PASS |
|
|
SWIMMING POOL BONDING INSPECTION PLEASE.; Phone #: ###-#### Internet Inspection Request from: Barry Kendall pool bonding ok, and slab ok to pour
|
ELE05-02217
| ELE-Aging Inspection | 3/28/2006 | 3/28/2006 | 3/28/2006 8:54:08 AM | | DONE |
|
|
called contr, suc, may not be ready till summer
|