Inspections for the day of: Tuesday, March 28, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01048 Electrical Rough-In3/28/20063/28/20063/28/2006 4:43:47 PMPPASS
Mike -- underground reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corr made,ok to cover u/g only
ELE06-00292 Electrical Rough-In3/28/20063/28/20063/28/2006 3:59:36 PMPFAIL
Scheduled by a contractor via Hello! on 3/28/2006 at 11:07:54 AM. Contact: ###-####. met owner, left corr notice,300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member 210.52(A)(1) receptacles shall be installed so that no point measured horizontally along the floor line is more than 6' from an outlet, BCC all make-up shall be done
ELE05-04290 Final3/28/20063/28/20063/28/2006 2:58:07 PMPFAIL
Robert -- location back of office; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, set up meeting when he calls back in, 314.23(C) enclosure mounted in finished surface shall be rigidly secured, BCC ceiling cover not approved
ELE04-01948 Final3/28/20063/28/20063/28/2006 2:07:18 PMPFAIL
please call 15 min prior to meet for access//dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met contractor, he asked for electronic corr notice rather than paper,110.26(F)(1)(a) there shall be no foreign piping systems in dedicated electrical space,width and depth of equipment from floor to structural ceiling, 314.25 each box shall have a cover
ELE06-01049 Electrical Rough-In3/28/20063/28/20063/28/2006 1:06:25 PMPFAIL
any questions please call Mike Dale; Phone #: ###-#### Internet Inspection Request from: Jeff Radford called, left message, left corr notice, 334.30 nm cable shall be stapled within 12" of boxes, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.70(2)(b) lighting outlet shall be switched and installed on exterior side of outdoor entrances or exits with grade level access, BCC no violations shall be retained, could not check attic, verify heater listing and load (wiring quite hot)
ELE06-00248 Electrical Rough-In3/28/20063/28/20063/28/2006 11:41:40 AMANH
UNDERGROUND CONDUIT; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contr, left message, couldn't get in gate, said to recall
ELE06-01048 Electrical Rough-In3/27/20063/28/20063/28/2006 10:10:35 AMAFAIL
Mike -- trench with a conduit; reconnecting svc to new mobile home; Western Village Mobile Park; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, told him conduit was not deep enough, did not leave corr notice, he will recall
ELE06-00938 Electrical Rough-In3/27/20063/28/20063/28/2006 9:42:49 AMAPASS
SWIMMING POOL BONDING INSPECTION PLEASE.; Phone #: ###-#### Internet Inspection Request from: Barry Kendall pool bonding ok, and slab ok to pour
ELE05-02217 ELE-Aging Inspection3/28/20063/28/20063/28/2006 8:54:08 AM DONE
called contr, suc, may not be ready till summer