ELE06-03238
| Conference | 3/28/2007 | 3/28/2007 | 3/28/2007 3:42:49 PM | P | DONE |
|
|
David; Phone #: ###-#### Internet Inspection Request from: Stacie Backus talked about afci, ckt extensions, 1 1/4", outside rear light, outlet spacing
|
ELE07-01008
| Electrical Rough-In | 3/28/2007 | 3/28/2007 | 3/28/2007 3:06:09 PM | P | PASS |
|
|
ed - pls call 30 prior; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric ok bath only, need to look at tub, since not there, chek new circuits from panel
|
ELE07-00023
| Final | 3/28/2007 | 3/28/2007 | 3/28/2007 2:30:56 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 3/28/2007 at 7:53:25 AM. Contact: ###-####. signed t/o card, left corr notice, nec 408.4 circuit directory shall be clear concise and specific as to its purpose, 605.7 multi-wire branch circuits shall be provided with a means to simultaneously disconnect all ungrounded conductors (partitions), 110.12(C) panel hasps shall be repaired, BCC no violations shall be retained, circuits shall operate
|
ELE07-00824
| Electrical Rough-In | 3/27/2007 | 3/28/2007 | 3/28/2007 1:31:48 PM | P | PASS |
|
|
CEILING RI Phone #: ###-#### ok to cover ceilings only
|
ELE07-00815
| Electrical Rough-In | 3/28/2007 | 3/28/2007 | 3/28/2007 1:12:22 PM | P | FAIL |
|
|
Jim pls call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Stacie Backus left corr notice,nec 300.14 at least 6" free conductor shall be left from where conductor enters box for splicing, told to call when fixed, downstairs area only for this part
|
ELE07-00905
| Final | 3/28/2007 | 3/28/2007 | 3/28/2007 12:43:53 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 3/28/2007 at 7:12:48 AM. Contact: ###-####. called contr, he did not call in this
|
ELE07-00937
| Final | 3/28/2007 | 3/28/2007 | 3/28/2007 12:31:22 PM | P | PASS |
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
ELE06-04665
| Electrical Rough-In | 3/26/2007 | 3/28/2007 | 3/28/2007 10:18:15 AM | A | PASS |
|
|
Boun; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, ric ok, tub ok
|
ELE07-00588
| Electrical Rough-In | 3/27/2007 | 3/28/2007 | 3/28/2007 9:41:59 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/27/2007 at 2:04:54 PM. Contact: ###-####. ok to cover ceilings, see cash wrap at final
|
ELE07-01006
| Final | 3/27/2007 | 3/28/2007 | 3/28/2007 9:14:43 AM | A | PASS |
|
|
Work performed by Aaron White. Phone #: ###-#### ok to final
|
ELE07-00321
| Electrical Rough-In | 3/27/2007 | 3/28/2007 | 3/28/2007 9:03:52 AM | A | CANC |
|
|
ted; Phone #: ###-#### upstairs inspection // Internet Inspection Request from: Victoria Beall see final, part, for time
|
ELE07-00321
| Final | 3/28/2007 | 3/28/2007 | 3/28/2007 9:03:17 AM | A | PART |
|
|
ted; Phone #: ###-#### upstairs inspection // Internet Inspection Request from: Victoria Beall contr accepting permit ele06-03008 adding rooms to 07 permit, upstairs only ok to final, will call for rest of permit ltr, should close 06 permit when all done
|
ELE07-00693
| Rough-In Permanent Service | 3/27/2007 | 3/28/2007 | 3/28/2007 8:32:25 AM | A | PASS |
|
|
Joe Phone #: ###-#### called contr, no plans on job, talked about jetted tubs, access, need to check at final, corrections made, ric ok, p/s u/g n ok
|
ELE06-03534
| Final | 3/27/2007 | 3/28/2007 | 3/27/2007 4:55:56 PM | A | CANC |
|
|
Call 1/2 hour before inspection to gain entry into the house. Plese call Chad at the listed number. thank you Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|