Inspections for the day of: Wednesday, March 28, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00475 FIRE-Final Inspection3/28/20073/28/20073/29/2007 11:42:14 AMPPASS
Necessary corrections have been verified for completion, life safety finaled.
FIR06-00523 INSP-Alarm Testing3/28/20073/28/20073/28/2007 5:06:22 PMPPART
Sprinkler monitoring only tested today, noted addressing at the WF switches in the riser room to correctly identify the system served.
FIR06-00101 INSP-Final Inspection3/27/20073/28/20073/28/2007 5:03:47 PMAFAIL
Missing heads in the building storage room, blocked pendent at the first floor east stair landing, missing escutcheons at several locations, painted head in the pool room, missing flex coulpings at the riser, wet head in the cooler at 33 deg. maintained, one head is overspaced at the ADA room, inspection concluded at the first floor due to the number of defficient items found.
BLD06-00660 FIRE-Final Inspection3/28/20073/28/20073/28/2007 4:53:06 PMPNR
Need project related fire alarm and sprinkler permit finals prior to BLD life safety inspection.
BLD06-02605 FIRE-Final Inspection3/27/20073/28/20073/28/2007 2:26:16 PMANR
Pending fire alarm work for smoke evac. system.
BLD06-00994 FIRE-Final Inspection3/28/20073/28/20073/28/2007 1:36:50 PMPPASS
Fire life safety finaled, inspection passed.
FIR05-00536 INSP-Sprinkler Rough-in/Hydro3/27/20073/28/20073/28/2007 1:34:33 PMAPART
Fire sprinklers are approved for cover at the 1st floor chapel and chaplains office, also reinspected 5th floor RR which was missing a head and one hanger at an arm-over above a hard lid.
BLD07-00475 FIRE-Final Inspection3/27/20073/28/20073/28/2007 11:01:25 AMAFAIL
Remove the manual thumbturn at the back exit door and provide approved exiting hardware.
MIS07-00057 FIR-Final3/27/20073/28/20073/28/2007 10:33:08 AMAFAIL
Need to provide a current annual inspection for the existing fire sprinkler system to be completed by a licensed fire sprinkler contractor, provide one additional PFE for the upstairs office, remove the manual thumbturn on the main entry/exit door.
FIR07-00163 INSP-Sprinkler Rough-in/Hydro3/27/20073/28/20073/28/2007 10:30:02 AMAPART
The UG fire supply line stub-in and IBR are approved for cover.