Inspections for the day of: Thursday, March 28, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00414 ELE-Aging Inspection3/28/20133/28/20134/1/2013 3:41:50 PM DONE
still under construction
GCE13-00049 GCE-Final3/28/20133/28/20133/28/2013 3:40:44 PMPFAIL
(Mandatory Inspection) Jeff ###-#### Signage for the emergence shut off switch not complete. Will final when complete.
GCE13-00049 GCE-Rough-In3/28/20133/28/20133/28/2013 3:40:13 PMPPASS
(Mandatory Inspection) Jeff ###-#### Propane dispenser rough in ok
ELE13-00452 Final3/27/20133/28/20133/28/2013 3:01:27 PMPPASS
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy
Final ok no card posted
ELE13-00353 Final3/22/20133/28/20133/28/2013 2:14:53 PMPPASS
access code is 5555, thx! Phone #: ###-#### >> Inspection requested via web by Stephen Kren Final ok
GCE13-00044 GCE-Rough-In3/28/20133/28/20133/28/2013 1:19:13 PMPDONE
Retro Electric ###-####; requested consultation with inspection Conference on code requirements for mobile home rewire.
GCE13-00044 GCE-Permanent Service3/28/20133/28/20133/28/2013 12:47:08 PMPPASS
Retro Electric @ ###-#### p/s o/h rec ok
ELE12-02402 Final3/27/20133/28/20133/28/2013 10:17:34 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast
Final ok
ELE12-02751 Final3/27/20133/28/20133/28/2013 9:45:11 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast
Final ok
ELE13-00337 Final3/27/20133/28/20133/28/2013 9:27:06 AMAPASS
kenny or todd Phone #: ###-#### Final ok
ELE11-02841 Final3/21/20133/28/20133/28/2013 9:08:25 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Matthew White Addressed aging permit on 3-21-13 drove by and inspected on that date. Final ok
ELE13-00670 Rough-In Permanent Service3/22/20133/28/20133/28/2013 9:06:09 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Stephen Kren
Rough in ok cover p/s u/g n ok
GCE12-00080 GCE-Final3/27/20133/28/20133/28/2013 8:41:40 AMAFAIL
Erin @ ###-####
Call for access
-Exterior and interior emergency lighting not installed as noted on print.
-Additional show room outlets required 210.62
-All electrical boxes shall have device covers.
- Panel cover not installed.
-Bathroom receptical shall be GFCI proteced and secured