Inspections for the day of: Monday, March 28, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03316 Electrical Rough-In3/28/20163/28/20163/28/2016 2:09:12 PMPPASS
SE-17,18 and IR-1 power and controls Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok for de watering pumps in vault. All SO cords spliced to bare conductors from submersable pumps connections ok
ELE15-01348 Conference3/28/20163/28/20163/28/2016 2:03:31 PMPDONE
Level 3 Stack 3 Smoke Fire Damper Motor accessibility Phone #: ###-#### Inspection requested via web by Tom Betty fire smoke damper INSIDE duct work not " readily accessable" as per requirments in NEC article 100. Access panel not designed for physically accessing damper. Unsafe confined space not meeting requirments in NEC110-26(C)(1)
ELE16-00679 Final3/28/20163/28/20163/28/2016 1:05:02 PMPPASS
Project is ready for final electrical inspection. Phone #: ###-#### Inspection requested via web by Del Renken final ok
ELE16-00951 Permanent Service3/28/20163/28/20163/28/2016 12:34:42 PMPPASS
Phone #: ###-#### Inspection requested via web by danny perrine p/s o/h n ok
ELE16-00925 Electrical Rough-In3/28/20163/28/20163/28/2016 11:24:14 AMPPASS
Lee Phone #: ###-#### r/i walls ok phase 1 ( relocate security check area)
ELE15-03347 Final3/25/20163/28/20163/28/2016 10:23:20 AMAPASS
Bob Phone #: ###-#### final ok ul listed and disconnect
ELE15-03347 Electrical Rough-In3/28/20163/28/20163/28/2016 10:12:39 AMPPASS
Bob Phone #: ###-#### r/i ok sign power
ELE16-00744 Rough-In Permanent Service3/25/20163/28/20163/28/2016 9:38:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn r/i ok p/s u/g n ok
ELE16-00936 Rough-In Permanent Service3/25/20163/28/20163/28/2016 9:18:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk r/i ok p/s u/g n ok
ELE16-00925 Electrical Rough-In3/25/20163/28/20163/28/2016 8:43:03 AMANH
Lee Phone #: ###-#### called twice to get directions no answer
ELE16-00117 Final3/25/20163/28/20163/28/2016 8:10:17 AMAPASS
Kenny Phone #: ###-#### corrections made final ok permanent occupancy ok