ELE17-01563
| Final | 3/27/2018 | 3/28/2018 | 3/28/2018 2:53:39 PM | A | PASS |
|
|
Install 1 set of letters reading Fowler and 1 set of letters reading Parking. ALL PRIMARY POWER BY OTHERS Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
|
ELE17-01563
| Electrical Rough-In | 3/27/2018 | 3/28/2018 | 3/28/2018 2:53:13 PM | A | PASS |
|
|
Install 1 set of letters reading Fowler and 1 set of letters reading Parking. ALL PRIMARY POWER BY OTHERS Phone #: ###-#### Inspection requested via web by Ken Olsen Listing and disconnecting means confirmed rough in ok cover
|
ELE18-01160
| Electrical Rough-In | 3/27/2018 | 3/28/2018 | 3/28/2018 2:23:16 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Hardlid for bathroom off common corridor for coffee shop and salon rough in ok cover
|
ELE17-04117
| Final | 3/27/2018 | 3/28/2018 | 3/28/2018 1:54:05 PM | P | PASS |
|
|
please contact Matt Burns with any questions or concerns
Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Final ok
|
ELE18-01170
| Temporary Service | 3/28/2018 | 3/28/2018 | 3/28/2018 1:32:51 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s o/h n ok
|
ELE18-01133
| Temporary Service | 3/27/2018 | 3/28/2018 | 3/28/2018 11:23:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE18-01134
| Temporary Service | 3/27/2018 | 3/28/2018 | 3/28/2018 11:22:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE18-01092
| Rough-In Permanent Service | 3/27/2018 | 3/28/2018 | 3/28/2018 10:47:20 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Installation not complete. Missed recessed con in kitchen area. 314.25- Recessed can junction box covers shall be installed to totally enclose box. Upstairs can back cover not installed as per manufacturers instructions. 300.4- Nail plates needed in kitchen under switch. WUI zone A- Outdoor recessed con fire barriers not complete at time of inspection.
|
ELE18-00491
| Electrical Rough-In | 3/27/2018 | 3/28/2018 | 3/28/2018 9:32:40 AM | P | PASS |
|
|
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen IT room hardlid only rough in ok cover
|
ELE18-01014
| Rough-In Permanent Service | 3/27/2018 | 3/28/2018 | 3/28/2018 8:55:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|