BLD19-00497
| FIRE-Conference | 3/28/2019 | 3/28/2019 | 3/28/2019 2:35:09 PM | P | DONE |
|
|
Owner had questions on difference between the night lights and the emergency lights.
|
FIR18-00804
| INSP-Conference | 3/28/2019 | 3/28/2019 | 3/28/2019 1:34:51 PM | P | DONE |
|
|
24 hour air test for C wing started at 1:30 with 48psi on the guage.
Richard Clark is the contact. He would like a 24-hour air test for wing C, we just weren''t sure which option to put it under. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00732
| INSP-Final Inspection | 3/26/2019 | 3/28/2019 | 3/28/2019 12:41:21 PM | A | FAIL |
|
|
Resubmit plans that show entire scope of work that includes all devices in all buildings. Devices shall annunciate by the building address. Installation shall meet NFPA 72. Provide updated battery and notification circuit calculations. Separate remote annunciators maybe required for each building. Lightning protection may be required for circuits connecting each building. All buildings may require riser room pull stations. The horns on the exterior of the building may not be required.
Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
|
FIR18-00882
| INSP-Sprinkler Rough-in | 3/27/2019 | 3/28/2019 | 3/28/2019 12:27:02 PM | A | PASS |
|
|
overhead rough-in passed. Piping above hardlids can be covered. The wood above the ceiling in the west end corridor will need to be addessed. Riser is not built yet. // Rick Phone #: ###-####
|
BLD18-02967
| FIRE-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 10:32:23 AM | A | PART |
|
|
Struvite level 1 catwalk life safety passed. Fire extinguisher has been added.
Joe Phone #: ###-####-please call 30 minutes prior to meet
|
NAF19-00025
| INSP-Final | 3/27/2019 | 3/28/2019 | 3/28/2019 10:22:56 AM | A | DONE |
|
|
Permit finaled
Call prior to going Phone #: 2088304123 >> Inspection requested via mobile web by Rick
|
NAF18-00129
| INSP-Final | 3/27/2019 | 3/28/2019 | 3/28/2019 8:58:10 AM | A | DONE |
|
|
Life safety passed. I spoke to the contractor about the need for an occupancy permit as per the scope of work for any tenants moving in.
Call prior to going Phone #: 20872714 >> Inspection requested via mobile web by Brad
|
NAF19-00040
| INSP-Final | 3/27/2019 | 3/28/2019 | 3/28/2019 8:56:45 AM | A | DONE |
|
|
Life safety passed
Call prior to going Phone #: 2085099202 >> Inspection requested via mobile web by Sally Oleary
|
BLD17-04568
| FIRE-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 8:39:13 AM | A | PASS |
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by Bob Thornton
|
FIR19-00116
| INSP-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 8:38:51 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Ken Webster
|